Caution, Maintenance and, Protocol – Edwards Signaling 5530M-485 User Manual
Page 3

P/N 3100345 ISSUE 2
PAGE 3
CAUTION
CAUTION
CAUTION
CAUTION
CAUTION
Ensure that power is disconnected before cleaning inside of
unit.
Maintenance and
Maintenance and
Maintenance and
Maintenance and
Maintenance and T
T
T
T
Test
est
est
est
est
Examine the unit semi-annually for accumulation of dirt.
Clean if necessary.
Protocol
Protocol
Protocol
Protocol
Protocol
1.0
Setting Unit Address and Network Baud Rate
1.1
Locate the 8-position dip switch, S1, on the top edge of the RS485 COMM board (Figure 6).
1.2
Unit address range is 00-1F hex. (00-31 decimal). Refer to Table 2.2 for unit address configuration. Set S1
positions 1-5 for the desired unit address configuration.
Table 2.2 Unit Address Switch Configuration
Unit Address
S1-1
S1-2
S1-3
S1-4
S1-5
Hex
Decimal
00
00
OPEN
OPEN
OPEN
OPEN
OPEN
01
01
CLOSED
OPEN
OPEN
OPEN
OPEN
02
02
OPEN
CLOSED
OPEN
OPEN
OPEN
03
03
CLOSED
CLOSED
OPEN
OPEN
OPEN
04
04
OPEN
OPEN
CLOSED
OPEN
OPEN
05
05
CLOSED
OPEN
CLOSED
OPEN
OPEN
06
06
OPEN
CLOSED
CLOSED
OPEN
OPEN
07
07
CLOSED
CLOSED
CLOSED
OPEN
OPEN
08
08
OPEN
OPEN
OPEN
CLOSED
OPEN
09
09
CLOSED
OPEN
OPEN
CLOSED
OPEN
0A
10
OPEN
CLOSED
OPEN
CLOSED
OPEN
0B
11
CLOSED
CLOSED
OPEN
CLOSED
OPEN
0C
12
OPEN
OPEN
CLOSED
CLOSED
OPEN
0D
13
CLOSED
OPEN
CLOSED
CLOSED
OPEN
0E
14
OPEN
CLOSED
CLOSED
CLOSED
OPEN
0F
15
CLOSED
CLOSED
CLOSED
CLOSED
OPEN
10
16
OPEN
OPEN
OPEN
OPEN
CLOSED
11
17
CLOSED
OPEN
OPEN
OPEN
CLOSED
12
18
OPEN
CLOSED
OPEN
OPEN
CLOSED
13
19
CLOSED
CLOSED
OPEN
OPEN
CLOSED
14
20
OPEN
OPEN
CLOSED
OPEN
CLOSED
15
21
CLOSED
OPEN
CLOSED
OPEN
CLOSED
16
22
OPEN
CLOSED
CLOSED
OPEN
CLOSED
17
23
CLOSED
CLOSED
CLOSED
OPEN
CLOSED
18
24
OPEN
OPEN
OPEN
CLOSED
CLOSED
19
25
CLOSED
OPEN
OPEN
CLOSED
CLOSED
1A
26
OPEN
CLOSED
OPEN
CLOSED
CLOSED
1B
27
CLOSED
CLOSED
OPEN
CLOSED
CLOSED
1C
28
OPEN
OPEN
CLOSED
CLOSED
CLOSED
1D
29
CLOSED
OPEN
CLOSED
CLOSED
CLOSED
1E
30
OPEN
CLOSED
CLOSED
CLOSED
CLOSED
1F
31
CLOSED
CLOSED
CLOSED
CLOSED
CLOSED
The Adaptatone should be tested annually or as required
by the authority having jurisdiction to ensure continuous
service.