P/N 3100345 ISSUE 2

PAGE 13

Figure 6. PC Board Locations

Figure 7. Tone Programming

Switch

Tone

Description

1

2

3

4

5

HEX

No Tone

00

Ding-Dong

Percussive pairs of 700 and 570 Hz tones, each damped to zero

01

Warble

575 and 770 Hz alternately, 87 ms each

02

Siren

600-1250 Hz up and down sweep in 8 seconds and repeat

03

Stutter

Percussive 470 Hz, 83 ms on, 109 ms off

04

Slow Whoop

600-1250 Hz upward sweep in 4 seconds and repeat

05

Beep

470 Hz, 0.55 seconds on, 0.55 seconds off

06

Chime 1

700 Hz percussive repeat at 1 Hz

07

Fast Whoop

600-1250 Hz upward sweep in 1 second and repeat

08

Hi/Lo

780 to 600 Hz alternately, 0.52 seconds each

09

Rapid Siren

600-1250 Hz up and down sweep in 0.25 seconds and repeat

0A

Yeow

1250-600 Hz downward sweep in 1.6 seconds and repeat

0B

Horn

470 Hz continuous

0C

Air Horn

370 Hz continuous

0D

Dual Tone

450-500 Hz, 0.4 to 0.5 second cycle

0E

Chime 2

575 Hz percussive repeat at 1 Hz

0F

Westminster

Two measures, 411 Hz, 520 Hz, 407 Hz, 312 Hz

10

Three Blind Mice

Four Measures, 787 Hz, 714 Hz, 625 Hz, 952 Hz, 333 Hz

11

Phasor

416-625 Hz up and down sweep in 13 ms and repeat

12

Telephone

570 and 770 Hz alternately, 50 ms each for 1.2s, 1.5s delay and repeat

13

Staircase

440-2000 Hz up and down steps, 750 ms delay and repeat

14

3 Tone Alert

463, 641 and 896 Hz, 200 ms each, 1 second delay and repeat

15

Presignal Chime

470 Hz percussive repeat at 1.5 Hz, followed by Message 1

16

NFPA Whoop

422-775 Hz, upward sweeps, 850 ms each, 1 second delay and repeat

1B

3 Pulse Horn

470 Hz, 3 0.5 second pulses separated by 0.5 seconds followed

1C

by a 1.5 second delay and repeat--For Evacuation Use Only

3 Pulse Air Horn

370 Hz, 3 0.5 second pulses separated by 0.5 seconds followed

1D

by a 1.5 second delay and repeat--For Evacuation Use Only

3 Pulse Dual Tone

450-500 Hz, 0.4 to 0.5 second cycle, 3 0.5 second pulses separated

1E

by 0.5 seconds followed by a 1.5 second delay and repeat--For
Evacuation Use Only

3 Pulse Chime 2

575 Hz, 3 0.5 second pulses separated by 0.5 seconds followed

1F

by a 1.5 second delay and repeat--For Evacuation Use Only

CAUTION

CAUTION

CAUTION

CAUTION

CAUTION

The use of evacuation signals on this product, that is not specifically Listed for
Fire Alarm Use, is subject to the approval of the Authority Having Jurisdiction.

RS485 COMM
Board

Potentiometer for
Volume Adjustment

Processor Board

EARTH

-RELAY

+RELAY

-TX/RX

+TX/RX