Specifications
Edwards halogen models, 48SIN and 48FIN, are designed for use
where increased light output is required. The 20 watt halogen
bulbs are rated by the manufacturer at 226 lumens. The 25 watt
halogen bulbs are rated at 175 lumens.
Edwards 48FLED long life, flashing LED models are effective in
high noise level areas, especially where ear protection must be
worn and a visual status indicator is required. Edwards 48SLED
long life, steady-on LED models are suited for light duty appli-
cations where a continuous steady-on status indicator is required
and where ambient noise makes audible signals difficult to hear.
The 48 series signals can be mounted on 1/2" (13mm) NPT con-
duit (indoor or outdoor) or direct surface mounted (indoor). For
outdoor (weatherproof) installation, the signals must be conduit
mounted with their lens facing directly up. When installing in-
doors, these signals can be mounted in any position.
PLC Compatibility
The electrical input load requirements for PLC compatible sig-
naling devices are listed in Table 1. Signaling devices may be
directly connected to output cards that meet these requirements.
Figure 1. Conduit Mounting
Catalog
Electrical
Lamp
Number
Rating
Ratings
48SIN(*)-E1
12V DC
188 Lumens
†
1.0A
1,520 hr.
‡
48SIN(*)-G1-20WH
24V DC
226 Lumens
†
0.80A
20,000 hr.
‡
48SIN(*)-G5-20WH
24V 50/60 Hz
226 Lumens
†
0.80A
20,000 hr.
‡
48SIN(*)-N5-25WH
120V 50/60 Hz
175 Lumens
†
0.20A
20,000 hr.
‡
48SLED(**)-G1
24V DC
100,000 hr.
‡
0.062A
48SLED(**)-N5
120V 50/60 Hz
100,000 hr.
‡
0.022A
48FIN(*)-E1
12V DC
188 Lumens
†
1.0A
1,520 hr.
‡
48FIN(*)-G1-20WH
24V DC
226 Lumens
†
0.80A
25,000 hr.
‡
48FIN(*)-G5-20WH
24V 50/60 Hz
226 Lumens
†
0.80A
25,000 hr.
‡
48FIN(*)-N5-25WH
120V 50/60 Hz
175 Lumens
†
0.20A
25,000 hr.
‡
48FLED(**)-G1
24V DC
100,000 hr.
‡
0.062A
48FLED(**)-N5
120V 50/60 Hz
100,000 hr.
‡
0.022A
*Specify color of lens by adding one of the following letters to the cat.
number: A-amber, B-blue, C-clear, G-green, M-magenta, or R-red.
**Specify color of lens by adding one of the following letters to the cat.
number: A-amber, B-blue, G-green, or R-red.
†
Bulb manufacturer's Lumen rating.
‡
Projected lamp life based on manufacturer's calculated lamp life at 65
fpm and 50% duty cycle.
Lens
Mounting base
and lamp
support plate
1/2“ (13mm)
NPT conduit
(not supplied)
To field wiring
Locking
Mechanism
Description
The Catalog Series 48 Adaptabeacon signal is a UL and cUL listed
signaling appliance in a NEMA 4X enclosure. The signals are
suitable for indoor or outdoor (weatherproof) installation and are
available in AC and DC models as listed above.
Table 1. PLC Compatibility
Operating
Maximum off state
Continuous on
Surge (inrush/duration)
Cat. No.
voltage*
leakage current (mA)
current (mA)
(A/ms**)
48SIN( )-G1-20WH
24V DC
25
800
0.9/1
48SIN( )-N5-25WH
120V AC
25
200
0.8/8
48SLED( )-G1
24V DC
4
65
0.07/1
48SLED( )-N5
120V AC
5
25
0.09/8
48FIN( )-G1-20WH
24V DC
25
800
2.2/100
48FIN( )-N5-25WH
120V AC
25
200
1.3/8
48FLED( )-G1
24V DC
4
65
0.07/1
48FLED( )-N5
120V AC
5
25
0.09/8
*All AC volts at 60 Hz
**Amps/milliseconds