Regulatory information, Contact information – Edwards Signaling 5532M User Manual
Page 10
10 / 10
P/N 3100010 • REV 7 • ISS 04AUG10
Tone
SW 4-6 SW 4-5 SW 4-4 SW 4-3 SW
4-2 SW4-1 Description
Hex
NFPA Whoop
OFF
ON
ON
OFF
ON
ON
Three 422 – 775 Hz upward sweeps, 850 ms each, 1 s
delay and repeat
1B
3 Pulse Horn*
OFF
ON
ON
ON
OFF
OFF
470 Hz, 3 0.5 s pulses separated by 0.5 s followed by
1.5 s delay and repeat
1C
3 Pulse Air Horn*
OFF
ON
ON
ON
OFF
ON
370 Hz, 3 0.5 s pulses separated by 0.5 s followed by
1.5 s delay and repeat
1D
3 Pulse Dual
Tone*
OFF
ON
ON
ON
ON
OFF
450 – 500 Hz, 0.4 to 0.5 s cycle, 3 0.5s pulses
separated by 0.5 s followed by 1.5 s delay and repeat
1E
3 Pulse Chime 2*
OFF
ON
ON
ON
ON
ON
575 Hz, 3 0.5 s pulses separated by 0.5 s followed by
1.5 s delay and repeat
1F
European
Police ON OFF OFF OFF OFF
OFF 969
Hz and 800 Hz alternately 0.250 s each
20
European Fire
ON
OFF
OFF
OFF
OFF
ON
982 Hz and 864 Hz downward sweep in 0.134 s
21
European Slow
Whoop
ON
OFF
OFF
OFF
ON
OFF
658 – 1312 Hz upward sweep in 3 s followed by 0.5 s
delay and repeat
22
European General
ON
OFF
OFF
OFF
ON
ON
1087 Hz for 0.5 s followed by 0.5 s delay and repeat
23
European Toxic
ON
OFF
OFF
ON
OFF
OFF
982 Hz continuous
24
European Police 2
ON
OFF
OFF
ON
OFF
ON
554 Hz and 440 Hz alternately, 0.8 s each
25
European Stutter
ON
OFF
OFF
ON
ON
OFF
3876 Hz for 0.146 s followed by 0.102 s delay and
repeat
26
European Sweep
ON
OFF
OFF
ON
ON
ON
1315 Hz – 413 Hz downward sweep in 1.17 s and
repeat
27
Telephone
2
ON OFF ON OFF OFF
OFF Alternate tones at 567 Hz and 326 Hz
28
Buzzer
ON OFF ON OFF OFF
ON 1315
Hz
and
746 Hz alternating for 0.003 s each
29
Genesis Horn Cont
ON
OFF
ON
OFF
ON
OFF
Continuous Genesis horn
2A
Genesis Horn
Temp
ON OFF ON OFF ON
ON Temporal
Genesis
horn
2B
Warning
1
ON OFF ON ON OFF
OFF 1207
Hz and 493 Hz, alternately 0.002 s each
2C
Warning
2
ON OFF ON ON OFF
ON 2336
Hz and 493 Hz, alternately 0.005 s each
2D
Warning 2 Beep
ON
OFF
ON
ON
ON
OFF
0.500 s of 2336 Hz and 493 Hz each alternating for
0.005 s followed by 1 s delay
2E
Caution
ON
OFF
ON
ON
ON
ON
453 Hz for 0.040 s, 235 Hz for 0.020 s, 235 Hz for 0.160
s, 260 Hz for 0.050 s, 260 Hz for 0.1009 s, 235 Hz for
0.050 s
2F
Multi-tone
ON
ON
OFF
OFF
OFF
OFF
376, 357, 352, 382, 355, 375, 384, 375 and 364 Hz
alternately on for 0.050 s
30
Attention
ON
ON
OFF
OFF
OFF
ON
2232, 4545, 3704, 2777, 4347, 3704, 2500 Hz
alternately on for 0.003 s
31
High Freq. Steady
Alert
ON ON OFF OFF ON OFF 2500
Hz
continuous
32
High Freq. Fast
Siren
ON
ON
OFF
OFF
ON
ON
2500 – 3048 Hz up and down sweep in 0.130 s
33
High Freq. Slow
Siren
ON
ON
OFF
ON
OFF
OFF
2500 – 3048 Hz up and down sweep in 0.500 s
34
DIN PFEER
ON
ON
OFF
ON
OFF
ON
Ramp downward from 1336 Hz to 522 Hz in 1.2 s and
repeat
35
NF S 32 001
ON
ON
OFF
ON
ON
OFF
584 Hz for 0.100 s and 461 Hz for 0.400 s
36
Ode to Joy
ON
ON
OFF
ON
ON
ON
6.45 s of melody followed by 1 s delay and repeat
37
Twinkle Little Star
ON
ON
ON
OFF
OFF
OFF
13.2 s of melody followed by 1 s delay and repeat
38
Dueling Banjos
ON
ON
ON
OFF
OFF
ON
10.84 s of melody followed by 1 s delay and repeat
39
La Cucaracha
ON
ON
ON
OFF
ON
OFF
7.10 s of melody followed by 1 s delay and repeat
3A
Yellow Rose of TX
ON
ON
ON
OFF
ON
ON
19.34 s of melody followed by 1 s delay and repeat
3B
*3 Pulse Tones are for Evacuation Use Only
CAUTION: The use of evacuation signals on this product, that is not specifically listed for fire alarm use, is subject to the approval
of the authority having jurisdiction.
Regulatory information
Edwards
Signaling
Edwards, A Division of UTC Fire & Security
Americas Corporation, Inc.
8985 Town Center Parkway, Bradenton, FL
34202, USA
Contact information
For contact information, see www.edwardssignaling.com.