beautypg.com

Axis – Edwards Signaling 106DEXST-FJ User Manual

Page 4

background image

P/N 3100101 ISSUE 6

WALL

BRACKET

MOUNTING

ANGLE

(DEGREES)

VERTICAL

PLANE

HORIZONTAL

PLANE

zero

100%

100%

5

90%

90%

10

90%

90%

15

90%

90%

20

90%

90%

25

90%

90%

30

90%

75%

35

65%

75%

40

46%

75%

45

34%

75%

50

27%

55%

55

22%

45%

60

18%

40%

65

16%

35%

70

15%

35%

75

13%

30%

80

12%

30%

85

12%

25%

90

12%

25%

Compound

45

24%

UL1971 REQUIRED

DISPERSION AS % OF CD

RATING

0

10

20

30

40

50

60

70

80

90

100

-90

-85 -80 -75

-70

-65

-60

-55

-50

-45

-40

-35

-30

-25

-20

-15

-10

-5

0 degrees

5

10

15

20

25

30

35

40

45

50

55

60

65

70

75

80

85

90

TYPICAL CD

UL REQUIRED CD
FOR 35 RATING

0

10

20

30

40

50

60

70

80

90

100

180

175

170

165

160

155

150

145

140

135

130

125

120

115

110

105

100

95

90

85

80

75

70

65

60

55

50

45

40

35

30

25

20

15

10

5

degrees

0

5

10

15

20

25

30

35

40

45

50

55

60

65

70

75

80

85

90

95

100

105

110

115

120

125

130

135

140

145

150

155

160

165

170

TYPICAL CD

UL REQUIRED CD
FOR 55 RATING

CEILING

MOUNTING

ANGLE

(DEGREES)

0

100%

5

90%

10

90%

15

90%

20

90%

25

90%

30

75%

35

75%

40

75%

45

75%

50

55%

55

45%

60

40%

65

35%

70

35%

75

30%

80

30%

85

25%

90

25%

Compound 45

24%

UL1971

REQUIRED

X & Y PLANE
DISPERSION

AS % OF CD

RATING

Figure 5. Light Output Patterns for 105DHISTC-FJ (Unit with clear lens only)

Effective Candela Light Output for Wall Bracket Mount

Vertical Plane

(Zero degree angle at side of globe)

Effective Candela Light Output for Ceiling Mount

X & Y Planes

(Zero degree angle at bottom of of globe)

UL 1971 Hearing Impaired: 35 cd wall
UL 1638 General Utility: 35 cd at 0

o

axis

UL 1971 Hearing Impaired: 55 cd ceiling
UL 1638 General Utility: 94 cd at 0

o

axis