Edwards Signaling 106DEXST-FJ User Manual
Page 3
P/N 3100101 ISSUE 6
Table 3. 106DEX AdaptaBeacon Strobe Light Replacement Parts
Mounting
Replacement
Cat. No.
Method
Strobe
106DEXPSTC-FJ
Pendant
Cat. No.
Figure 1
92-ST
106DEXCSTC-FJ
Ceiling
Figure 2
106DEXBSTC-FJ
Bracket
Figure 3
Table 1. 106DEX AdaptaBeacon Strobe Light Electrical Specifications
Operating Current*
Initial Surge Inrush Current
Repetitive Surge Current
Voltage** RMS Current (A)
Mean Current (A)
Current (A)
Time (mS)
Current (A)
Time (mS)
20V DC
1.08
0.84
2.70
1.10
2.24
450
24V DC
0.95
0.69
2.97
1.13
2.21
400
28V DC
0.85
0.66
3.06
1.24
2.16
381
30V DC
0.83
0.64
3.14
1.27
2.14
360
*Use the operating current to establish the wire gauge and standby power requirements. Consult the control unit manufacturer to
determine surge and peak current effects and maximum number of strobes on the system.
**CAUTION: To prevent damage to the visual signal's internal circuit and to assure its continued proper functioning, DO
NOT operate the unit outside of the Special Application Voltage range of 20-30V DC.
Table 2. 106DEX AdaptaBeacon Strobe Light Specifications
Mounting
Conduit
Flash
Rated Light
Cat. No.
Method
Size
Rate
Output
106DEXPSTC-FJ
Pendant
3/4"
360° beam
55 cd/35 cd
Figure 1
NPT
of light at
per
106DEXCSTC-FJ
Ceiling
~65 fpm
Figure 5
Figure 2
106DEXBSTC-FJ
Bracket
Figure 3
Table 4. Supply Wire Temperature Markings
Ambient
Supply Wire
Temperature
Temperature Marking
40°C
75°C
55°C
90°C
65°C
105°C