beautypg.com

Edwards Signaling 106DEXST-FJ User Manual

Page 3

background image

P/N 3100101 ISSUE 6

Table 3. 106DEX AdaptaBeacon Strobe Light Replacement Parts

Mounting

Replacement

Cat. No.

Method

Strobe

106DEXPSTC-FJ

Pendant

Cat. No.

Figure 1

92-ST

106DEXCSTC-FJ

Ceiling

Figure 2

106DEXBSTC-FJ

Bracket

Figure 3

Table 1. 106DEX AdaptaBeacon Strobe Light Electrical Specifications

Operating Current*

Initial Surge Inrush Current

Repetitive Surge Current

Voltage** RMS Current (A)

Mean Current (A)

Current (A)

Time (mS)

Current (A)

Time (mS)

20V DC

1.08

0.84

2.70

1.10

2.24

450

24V DC

0.95

0.69

2.97

1.13

2.21

400

28V DC

0.85

0.66

3.06

1.24

2.16

381

30V DC

0.83

0.64

3.14

1.27

2.14

360

*Use the operating current to establish the wire gauge and standby power requirements. Consult the control unit manufacturer to
determine surge and peak current effects and maximum number of strobes on the system.
**CAUTION: To prevent damage to the visual signal's internal circuit and to assure its continued proper functioning, DO
NOT operate the unit outside of the Special Application Voltage range of 20-30V DC.

Table 2. 106DEX AdaptaBeacon Strobe Light Specifications

Mounting

Conduit

Flash

Rated Light

Cat. No.

Method

Size

Rate

Output

106DEXPSTC-FJ

Pendant

3/4"

360° beam

55 cd/35 cd

Figure 1

NPT

of light at

per

106DEXCSTC-FJ

Ceiling

~65 fpm

Figure 5

Figure 2

106DEXBSTC-FJ

Bracket

Figure 3

Table 4. Supply Wire Temperature Markings

Ambient

Supply Wire

Temperature

Temperature Marking

40°C

75°C

55°C

90°C

65°C