beautypg.com

System design – Edwards Signaling ReadySet User Manual

Page 21

background image

Chapter 3: Installation and configuration

ReadySET Aspirating Smoke Detection System Installers Handbook

13

System design

Pre-engineered piping designs simplify the installation of the detector pipe network.
The following criteria ensure that the airflow and transport times are within the design of
the detector. The design parameters listed below must be adhered to for all pre-
engineered pipe designs. Pre-engineered piping networks should not exceed the
transport time requirement of 120 seconds. During the system test, transport times are
often less than 55 seconds.

• The maximum of three elbows and one pipe tee can be used in any pipe network

design.

• When using a pipe tee, it must be located within 20 feet of pipe from the detector.

• All capillary tubes will have a maximum length of 3 feet and use a 9/64 inch

sampling hole size.

• The first sampling hole must be 10 feet or more from the detector.

• The use of sampling capillary tubes and sampling holes can be mixed in any

combination on the pipe network.

• On branch designs, the same number of sampling holes must be used on each

branch.


Table 1: Sample pipe network parameters

Total pipe
length

Max amount
elbows

Max sampling
points

Sampling
hole size

Capillary tube
sample hole size

End cap
hole

164 feet

3

10

1/8 inch

9/64 inch

5/32 inch

Note:

PipeCAD pipe modeling software is used to design pipe networks outside the

above parameters. Refer to the PipeCAD System Design and Installation User Manual for
complete instructions.

The ReadySET detector employs a fan designed to detect smoke in relatively small
areas. The ReadySET detector is not intended to protect large areas, or to sample from
areas where there may be any difference in airflow rates or pressure differentials. If
detection in environments conforming to these descriptions is required, other AIR-
Intelligence products should be used.

Always locate the sampling points in positions to which smoke may reasonably be
expected to travel. It is usually better to locate the sampling pipe directly in the airflow
(for example, across the return air register of an air conditioning unit).

Note:

There is no substitute for carrying out smoke tests prior to installation of pipework

to indicate suitable sampling point location.