beautypg.com

Specifications – Edwards Signaling E-2WIRE User Manual

Page 3

background image

P/N 3101192 • REV 03 • REB 25JAN13

3 / 4

Specifications

Communication line voltage

Maximum 20.6 V peak-to-peak

Current

Standby

Activated


350 μA

350 μA

Ground fault impedance

5 kΩ

Control panel input power (not
resettable)

12.4 to 28.3 VDC

Smoke power current

Standby

Alarm


17 mA
58 mA

Smoke detector current

3 mA

UL compatibility ID

0.0

Operating environment

Temperature

Humidity


32 to 120°F (0 to 49°C)
0 to 93% RH, noncondensing at 90°F
(32°C)

Storage temperature range

–4 to 140°F (–20 to 60°C)

Compatible electrical boxes

North American 4 inch square ×
2-1/2 in. (64 mm) deep 2 gang box
Standard 4 in. square box 1-1/2 in.
(38 mm) deep

Wire size

12, 14, 16, or 18 AWG wire (2.5, 1.5,
1.0, or 0.75 mm

2

) (Sizes 16 and 18

AWG are preferred)

Device address

01 to 64 (64 point control panel)
01 to 127 (127 point control panel)

Initiating device circuit (IDC)

EOL resistor value

Max. circuit resistance

Max. circuit capacitance


4.7 kΩ, (P/N: EOL-4.7)

50 Ω (25 Ω per wire)

0.1 μF