beautypg.com

Wiring – Edwards Signaling E-2WIRE User Manual

Page 2

background image

2 / 4

P/N 3101192 • REV 03 • REB 25JAN13

5. Mount the module on the electrical box using screws

provided with the electrical box.

6. Mount the wall plate on the module using #4-24 × 1/2 in.

(13 mm) self-tapping screws.

Figure 2: Module address

Insert

screwdriver

here

Figure 3: Module installation

Screw

4-24

screws

Module

Wall plate

Compatible

electrical box

Wiring

Wire in accordance with NFPA 72 and CAN/ULC-S524. Be
sure to observe the polarity of the wires as shown in Figure 4.

Figure 4: Module wiring

[3]

Style D (Class A)

[1] [2] [4]

Style B (Class B)

[1] [2] [4]

Typical

initiating

device

TB2

TB1

From

previous

device

To next
device

From control

panel (not

resettable)

24 V +

4.7 k EOLR

Used for

Class B only

SLC out (+)

SLC out

SLC in

SLC in (+)

SLC

DET. PWR.

(+)

(+)

(+)

(+)

+

+

RETURN

DET.

( )

( )

( )

( )

( )

24 V

( )

Notes
[1]

Maximum 25 Ω resistance per wire

[2] Maximum 12 AWG (2.5 sq. mm) wire; minimum 18 AWG (0.75 mm

2

) wire

[3] Refer to the control panel technical reference manual for wiring specifications
[4] Maximum 23.8 VDC at 35 mA