Edwards Signaling ANS Audio Notification System User Manual

Page 9

background image

P/N 3101179 • REV 03 • REB 28FEB13

9 / 12

Figure 6: Wiring for an addressable system using a relay module to activate the ANS and a monitor module for supervision

Unsupervised and power-limited

ADDRESSABLE

CONTROL MODULE

Supervised and power-limited

ADDRESSABLE

MONITOR MODULE

ADDRESSABLE

LOOP

NO

CLOSES FOR

ALARM ACTIVATION

24 Vdc

0.01 A max.

Addressable Modules must

be located within 20 ft. and

interconnection must be in

a conduit.

[2]

[2]

E

O

L

MONITOR MODULE

EOLR

E

O

L

MATCHING EOLR

(SPEAKER CIRCUIT)

A

B

TB1

TB3

TB2

P2

U6

S1

SN2

SN1

1 2 3

J2

J5

J1 [1]

1

2

70V 25V

+

+

+

+

1

2

3

4

5

6

7

8

1
2
3
4
5
6
7
8

1

2

3

4

5

6

7

8

9

10

11

Notes

[1] The jumper shorting blocks on J1

must be removed for this

application.

[2] Power and speaker connections

remain unchanged.