beautypg.com

Installation instructions, Wiring instructions, Terminal designations – Edwards Signaling ANS Audio Notification System User Manual

Page 2

background image

2 / 12

P/N 3101179 • REV 03 • REB 28FEB13

Model

ANS25

ANS50

ANS100

Battery charging capacity [2]

Minimum

24 V, 7 Ah

Maximum

24 V, 18 Ah

24 V, 18 Ah

24 V, 24 Ah

FACP NAC

circuit current

10 mA maximum

[1] Input current measurements are determined using test conditions

specified in UL 1711. Sine represents measurements made while the

unit produces a continuous, undistorted sine wave of 1 kHz into the

rated load of 25, 50, or 100 W at the rated output voltage. Alarm is the

average current the unit experiences delivering an alarm signal,

temporal whoop, to the rated load. Standby is the current draw of the

unit with all normal power on and auxiliary terminals fully loaded.

Battery standby is the current draw from the batteries on loss of power

in an otherwise normal standby state.
[2] All ANS cabinets hold two 12 V, 7 Ah batteries. Larger batteries

require an external battery cabinet.

Installation instructions

Ensure that all wiring and devices installed in the system meet

the following standards:

NFPA 70 National Electrical Code

NFPA 72 National Fire Alarm and Signaling Code

NFPA 101 Life Safety Code

Applicable state and local codes

Install this equipment in a clean, dry environment. Avoid

installation where the equipment could be subjected to

vibration. Remove all electronic assemblies from the enclosure

before drilling or punching the enclosure. Where possible,

make all cable entries from the rear or sides. Before making

any modifications to the enclosure, be certain that they will not

interfere with the assemblies or batteries.

Wiring instructions

Refer to Figure 1 for terminal designations, and to diagrams in

the “Applications” section for wiring diagrams.
1. Connect the speaker lines to TB1-5(+) and TB1-6(−).

Be sure to observe polarity and connect all speakers using

the same polarity. For Class A (Style Z) the returns are

TB1-7(−) and TB1-8(+).

Note:

When using 70 VRMS speakers, the speaker wiring

must be enclosed in grounded metal conduit.

2. Connect the microphone to connector P2.

If the microphone is not installed, ensure that switch

SN2-8 is in the OFF position.

3. Attach the appropriate EOLR for the FACP to TB3-3 and 4

and for the speaker circuit to TB3-5 and 6.
You must use EOLR value specified for the FACP

notification appliance circuit (NAC). See the FACP

installation instructions provided by the manufacturer.

Note:

if your system includes one or more ANSZS4B zone

splitters, the FACP EOLR must be relocated. See the

ANSZS4B installation sheet (P/N 3101185).

4. Connect the FACP signaling circuit to TB1-3(+) and

TB1-4(−), using the FACP alarm polarity.

5. Connect the mains power (120 Vac at 60 Hz) to the black

and white pigtail leads from transformer primary. Secure

the ground lead to the grounding stud in the cabinet.

6. Connect the battery wiring harness, Red(+) and Black(−).

Observe the correct polarity.
Use two 12 V batteries connected in series. (See

Figure 4.) If the unit does not have its own batteries and

relies on an external power supply with battery backup,

ensure that switch SN2-7 is in the OFF position.

Note:

Wiring for batteries is nonpower-limited. Maintain a

minimum spacing of 1/4 in. between power-limited wiring

and nonpower-limited wiring.
If the batteries must be located in a separate enclosure,

provide a separate conduit run for the battery wiring only.

7. When all power and circuits are connected, the green LED

turns on (and stays on) to indicate that the ANS is fully

operational and all circuits are normal.

Terminal designations

Refer to Figure 1 for the locations of the terminals.

Table 3: Terminal descriptions
Terminal

Description

TB1-1, -2

Power input 24 to 32 Vac/Vdc [1][4]

TB1-3, -4

FACP NAC input. 10 mA max. Alarm polarity is shown.

[1][4]

TB1-5, -6

Speaker loop, Style Y/Z (Class A/B start) [2][4]

TB1-7, -8

Speaker loop Style Z (Class A return) [2][4]

TB2-1

Circuit negative

TB2-2

Aux audio input. 0.5 Vrms nominal, 1 Vrms, 1 mA max.

[1][3]

TB2-3

Preamp in/out. 600 Ω, 0 dBm. [1][3][5]

TB2-4

Factory Programmable output [1][3][5]

TB2-5

Signal active [1][3][5]

TB2-6

Aux audio enable. +24 Vdc, 32 Vdc, 5 mA max. [1][3]

TB2-7

Aux signal activate. +24 Vdc, 32 Vdc, 5 mA max. [1][3]

TB2-8

Alarm voltage. +24 Vdc, 0.1 A when unit is in alarm

condition. [2][3][5]

TB2-9

Interrupted V+. +24 Vdc, 0.1 A. Disconnected in alarm

condition. [2][3]

TB2-10

V+. +24 Vdc, 0.1 A. [2][3]

TB2-11

Microphone PTT. +24 Vdc, 0.1 A. [5]

TB3-1, -2

Optional FACP supervisory circuit. See installation

instructions for details. 32 Vdc, 0.4 A max.). Must be

configured using J1. [1][4]

TB3-3, -4

FACP Signal/Supervisory circuit EOLR