Specifications, Table 3, Refer – Edwards Signaling 116DEGEX-FJ User Manual
Page 5
P/N 3101131 • REV 04.00 • ISS24JUN11
5 / 6
Specifications
Voltage
16 - 33 VDC / FWR
Max RMS operating
current*
0.505 A at 24 VDC Regulated**
0.683 A at 24 VDC FWR
Candela rating (without
guard)
Wall
Ceiling
60 cd
125 cd
Candela rating (with
guard)
Wall
Ceiling
51 cd
86 cd
Caution:
To prevent damage to the signal circuit and to
otherwise assure continued proper functioning, DO NOT
operate the unit outside of the regulated 24 VDC/FWR voltage
range of 16 – 33 VDC/V FWR.
*The Max RMS operating current is defined as the current rating over
the entire voltage range.
**The designation “Regulated 24” refers to the voltage range of 16 –
33 volts
Table 1: Compatible synchronization modules
Model names
Model numbers
Auto-sync output module
SIGA-CC1S
SIGA-CC1S-LG
SIGA-MCC1S
SIGA-MCC1S-LG
Model names
Model numbers
Genesis signal master – remote
mount
ADTG1M-RM
EG1M-RM
G1M-RM
G1M-RM-LG
MG1M-RM
XLSG1M-RM
ZG1M-RM
Table 2: 116 Class catalog numbers
Description
Catalog number
Housing color
Housing less mounting
module
116DEGEX-FJ
116DEGEX-FJ-R
Gray
Red
Ceiling mount module –
3/4” NPT
116EX-C
116EXR-C
Gray
Red
Pendant mount module –
3/4” NPT
116EX-P
116EXR-P
Gray
Red
Wall mount module (requires
use of ceiling mount module)
116EX-B
116EXR-B
Gray
Red
Table 3: Ratings
Ambient temp.
Supply wire temp.
marking
Class I, Div. 2
Groups A, B
Class I, Div. 1 & 2
Groups C, D
Class II & III, Div. 1
Groups E, F, G
Class II & III, Div. 2
Groups F, G
40°C
75°C
T2B (260°C)
T6 (85°C)
T4A (120°C)
T4A (120°C)
55°C
90°C
T2B (260°C)
T6 (85°C)
T4 (135°C)
T4 (135°C)
65°C
105°C
T2B (260°C)
T6 (85°C)
T3C (160°C)
T3C (160°C)