beautypg.com

Specifications – Edwards Signaling FSRRM24 Remote Relay Module User Manual

Page 3

background image

P/N 3101058 • REV 02 • REB 25JAN13

3 / 4

[3] If powered from an external supply, the supply must be

installed in the same room as the control panel and their
24 VDC commons (−) wired together.

4. Relay outputs are not supervised and do not provide

current limiting. Connect relays only to power-limited
sources.

5. Terminal marking indicates contact position when the relay

is deenergized.

Specifications


Voltage

18.8 to 27.3 VDC

Current

Standby

Alarm


10 mA (zone relay operation)
26 mA (common relay operation)
70 mA

Circuit capacitance

0.03 μF, max.

Circuit resistance

13 Ω, max.

Ground fault impedance 0 Ω

Relay outputs

Quantity
Type

Style
Contact rating


5
Common, zone, or programmable, and dry
contact or +24V output via jumper selection
Form C
30 Vdc at 1 A (resistive load)

Wire size

12 to 18 AWG (0.75 to 2.5 sq mm)

Mounting MFC-A

cabinet

Operating environment

Temperature
Relative humidity


0 to 49 °C (32 to 120 °F)
0 to 93% noncondensing