FSRRM24 Remote Relay Module

Installation Sheet

Description

The FSRRM24 provides five Form C relays that you can
configure as common relays, zone relays, or as programmable
relays to use with F-series fire alarm control panels. In
addition, you can configure the relays as dry contact relays or
as 24 VDC output relays.

LEDs provide visual indication when each relay is energized
and when the FSRRM24 is disabled.

The FSRRM24 includes a plastic snap track for mounting in an
MFC-A cabinet.

FSRRM24 remote relay modules are configured using the
jumpers described in the tables below.

Table 1: Disable output jumper

JP1 Description

ON

Disables all relays

OFF

Enables all relays

Table 2: Module type jumpers

JP2 JP3 JP4 JP5 Description

ON

OFF OFF OFF Five programmable relays (common

alarm or zone)

OFF

ON

OFF OFF Five zone relays (zones 6 to 10). This

setting is ignored on 3-zone and 5-
zone conventional F-Series control
panels.

OFF

OFF ON

OFF Five zone relays (zones 1 to 5)

JP2 JP3 JP4 JP5 Description

OFF

OFF OFF

ON

Relay 1: Common alarm
Relay 2: Common trouble
Relay 3: Common supervisory
Relay 4: Common monitor
Relay 5: Common power

Note:

Only one FSRRM24 module configured for common relay

operation is allowed per peripheral group.

Table 3: Group selection jumper

J6 Description

ON

Selects peripheral group 1

OFF

Selects peripheral group 2

Notes:

Only three FSRRM24 modules are allowed per peripheral

group on 3- and 5-zone control panels. Only four FSRRM24 modules
are allowed per peripheral group on 10-zone control panels.

Table 4: Output selection jumpers, J1 to J5

Position Description

1 to 2

+24V output

2 to 3

Dry contact

Installation

Install the FSRRM24 according to the instructions provided
below.

Caution:

Make sure all power is disconnected from the panel

before installing. Observe static-sensitive handling practices.