Wiring – Edwards Signaling FSRRM24 Remote Relay Module User Manual
Page 2
2 / 4
P/N 3101058 • REV 02 • REB 25JAN13
Figure 1: FSRRM24 mounting
To install the FSRRM24:
1. Mount the snap track on the MFC-A cabinet as shown in
Figure 1. Only two FSRRM24 modules are allowed per
MFC-A cabinet.
2. Insert the bottom edge of the FSRRM24 into the snap
track then press the top edge in until it snaps into place.
3. Configure the jumpers.
4. Verify that all wiring is free of opens, shorts, and ground
faults.
5. Connect the data and power wiring as shown Figure 2.
6. Energize the panel and confirm that all relays are in the
correct state before connecting the field wiring.
Note:
Normally all relays are deenergized. If a jumper is
installed on JP5, relays 1 and 5 are energized.
7. Connect the relay output wiring as shown Figure 3. Make
sure connection will not adversely affect controlled devices
(e.g. elevators, fans, etc.).
Note:
FSRRM24 remote relay modules will not operate
properly until detected by the control panel. For more
information, see the technical reference manual listed inside
the control panel door.
Wiring
Figure 2: Data and power wiring
Figure 3: Relay output wiring
Notes
1. All wiring is supervised and power-limited.
[2] AUX power supplied by the control panel can’t exceed
0.5 A. If more than 0.5 A is required, you must use a
power-limited and regulated 24 VDC auxiliary/booster
power supply that is UL/ULC Listed for fire protective
signaling systems.
MFC-A
Snap track
FSRRM24
C
C
To
next remote
module
From
control panel
J1
J2
J3
J4
J5
3
2
1
3
2
1
3
2
1
1
3
2
1
JP1
JP2 JP3 JP4 JP5
3
2
JP6
Regulated 24 VDC
from control panel or
external power supply
[2] [3]
C
C
N.U.
OUT 2
NC C NO
OUT 4
NC C NO
OUT 5
NC C NO
NO
NO
C
C
NC
NC
OUT 3
OUT1
J1
J2
J3
J4
J5
3
2
1
3
2
1
3
2
1
3
2
1
3
2
1
JP1
JP2 JP3 JP4 JP5
JP6
[4]