Specifications – Edwards Signaling F-DACT_F Digital Alarm Communicator User Manual
Page 4
4 / 4
P/N 3101038 • REV 03 • REB 25JAN13
Line 1 and Line 2 supervision duration
The Line 1 Supervision Duration and Line 2 Supervision
Duration options determine how long the dialer waits before
reporting a line cut or ground fault (if enabled) on the telephone
line connections. You can choose between 0 (off) and 200
seconds.
Default: 200 seconds
To change the Line 1 and Line 2 supervision duration:
1. Select Line 1 Supv Dur.
2. Enter a time between 0 and 200. 0 turns Line 1
supervision off
3. Select Line 2 Supv Dur.
4. Enter a time between 0 and 200. 0 turns Line 2
supervision off
Blind call dialing
The Blind Call Dialing option determines whether the dialer can
dial out without waiting for a dial tone.
Default: No
To enable blind call dialing:
1. Select Blind Call Dial.
2. Enter
Yes.
Line ground fault check
The Line Ground Fault Check option determines whether the
dialer supervises both telephone lines for ground faults.
Default: Yes
To disable telephone line ground fault supervision:
1. Select Line GF Check.
2. Enter
No.
Specifications
Phone line type
One or two loop-start lines on a public,
switched network
Phone line connector
RJ-31/38X (C31/38X). Two 7 ft plug cords
are shipped with the F-DACT(F).
FCC registration
number
US: GESAL01BFDACT
Ringer equivalence
number
0.1
Industry Canada
Registration number
IC: 3944-FDACT
Connection between
panel and F-DACT(F)
6-pin connector
Communication
formats
Contact ID (SIA DC-05) and EST 4/2 (SIA
DC-02 P3 with hexadecimal event codes)
Current
Standby
Alarm
65 mA at 24 VDC, nominal
107 mA at 24 VDC, nominal
Operating environment
Temperature
Relative
humidity
32 to 120°F (0 to 49°C)
0 to 93% noncondensing