P/N 3101038 • REV 03 • REB 25JAN13

Line 1 and Line 2 supervision duration

The Line 1 Supervision Duration and Line 2 Supervision
Duration options determine how long the dialer waits before
reporting a line cut or ground fault (if enabled) on the telephone
line connections. You can choose between 0 (off) and 200
seconds.

Default: 200 seconds

To change the Line 1 and Line 2 supervision duration:

1. Select Line 1 Supv Dur.

2. Enter a time between 0 and 200. 0 turns Line 1

supervision off

3. Select Line 2 Supv Dur.

4. Enter a time between 0 and 200. 0 turns Line 2

supervision off

Blind call dialing

The Blind Call Dialing option determines whether the dialer can
dial out without waiting for a dial tone.

Default: No

To enable blind call dialing:

1. Select Blind Call Dial.

2. Enter

Yes.

Line ground fault check

The Line Ground Fault Check option determines whether the
dialer supervises both telephone lines for ground faults.

Default: Yes

To disable telephone line ground fault supervision:

1. Select Line GF Check.

2. Enter

No.

Specifications


Phone line type

One or two loop-start lines on a public,
switched network

Phone line connector

RJ-31/38X (C31/38X). Two 7 ft plug cords
are shipped with the F-DACT(F).

FCC registration
number

US: GESAL01BFDACT

Ringer equivalence
number

0.1

Industry Canada
Registration number

IC: 3944-FDACT

Connection between
panel and F-DACT(F)

6-pin connector

Communication
formats

Contact ID (SIA DC-05) and EST 4/2 (SIA
DC-02 P3 with hexadecimal event codes)

Current
Standby
Alarm


65 mA at 24 VDC, nominal
107 mA at 24 VDC, nominal

Operating environment
Temperature
Relative

humidity


32 to 120°F (0 to 49°C)
0 to 93% noncondensing