background image

1600A-N4X

1600A-N4X Instruction Manual

Rev. 0.2

Page 19 of 38


NOTE: The 1600A Device # is in decimal format, and the serial address switch setting for the 600 or 700
Series Sensor is in hexadecimal format. This means that device number 10 decimal on the 1600A
corresponds to the 600 or 700 Series Sensor at address 0A hexadecimal.

4.1.5 4-20mA Output Setup


This menu entry is used to address Detcon AO-4 modules 4-20mA output.

NOTE: If there are no AO-4 modules being used, do not enter any device and address information on this
screen. Misinformation entered here will cause the controller to generate a ‘No Communication Fault’.

Figure 27 Set-up 4-20mA Outputs


Make sure to set each AO-4 module to a unique module address using the front panel switches. The values
should be as follows:

CH#

AO4 Address

01 thru 04

81 Hex

05 thru 08

85 Hex

09 thru 12

89 Hex

13 thru 16

8D Hex