Figure 10 Model DA-4 and 4-20mA Gas Sensor Connections

4-20mA

INPUT

COMM

M
S
D

L
S
D

Typical Sensors

Sensor 2

Sensor 1

Sensor 3

Sensor 4

Figure 11 Model DA-4 and 4-20mA Gas Sensors

RS-485 Modbus™ Gas Sensors

Connect the five wires from the Modbus™ gas sensors (Detcon Model 600 and Model 700 Series types) to the
din rail mounted terminals labeled RS-485 “A”, “B”, and “Shld” and VDC “+” and “-”. Note: the controller
power supply is only capable of handling 3Amps accumulative. If the external sensors plus the controller’s
internal modules exceeds this rating, only three wires (RS-485 “A”, “B”, and “Shld”) should be used and a
remote DC power source should be utilized to provide DC power for the remote mounted gas sensors.

NOTE: A 120

: end of line resistor should be installed on the last gas sensor in the serial loop to enhance

communications reliability.