beautypg.com

4 pressure measurement sequence for gage only unit – Condec UPC5010 User Manual

Page 8

background image

Operation

5

8. Optional - if the current (4.000 to 20.000 mA) measurement features are used, connect the provided

transducer test cable, (PN 55092), to the transducer test jacks (14).

When connected, the transducer test cable provides +32 VDC excitation on non-battery units, or +18 VDC
excitation on battery units. The internal impedance (load) is 10 ohms.

NOTE:

+ EXCITATION VOLTAGE will only operate while units power cord is plugged into AC wall outlet. Battery units

may be ordered special to obtain +28 VDC excitation.

The display scaling for these current measurements are as follows:

NOTE:

UPC5000/UPC5010 reads a 4-20 mA signal only, but will display as either 4-20 mA or 20-100 mV.

The test cable connector wiring is as follows:

NOTE:

Connector pin designations are for reference only, and are no longer a connector on newer units. See Figure 2-2

on page 4 (14).

2.3

Pressure Measurement Sequence for Absolute/Gage Unit

1. Check that the indicator on the right end of the display indicates desired mode (10). If not, momentarily

depress the ABS/GAGE switch (11) to obtain mode.

2. If operating unit in GAGE mode go to Section 2.4. If operating unit in ABSOLUTE mode go to Section

2.5.

2.4

Pressure Measurement Sequence for Gage Only Unit

NOTE:

See Figure 2-3 on page 6 when following these steps.

1. To apply pressure, close the

VENT

valve (8), approximately two turns, until it stops, then open the

COARSE ADJUSTMENT

valve (2) approximately 1/2 turn counter-clockwise until the numerical display

begins to move. The pressure may change rapidly until reaching approximately 90% of the desired final
value.

2. Use either the

COARSE ADJUSTMENT

(2) or

VENT

valve (8) to obtain a specific pressure reading. Both

provide precise control. As the pressure approaches the desired value, the valve being used for control
should be rotated slowly clockwise to its closed position.

3. To obtain exact pressure readings, slowly rotate the

VERNIER

control (13) knob in the direction required

(clockwise to increase pressure) as indicated by the electronic numerical display.

4. The transducer current measurement can be displayed at any time by placing the

DISPLAY SELECT

switch (16) to its

CURRENT

position.

SWITCH POSITION

DISPLAY READING

Current

0-20.000 mA by 0.005 mA

*

Voltage

0-100.00 mV by 0.02 mV

Table 2-1. Display Select Switch (16)

CONNECTOR PIN DESIGNATION

FUNCTION

A

+ VDC

B

+ SIGNAL

C

NOT USED

D

VOLTAGE & SIGNAL COMMON

Table 2-2. Transducer Test Cable (PN 55092)

This manual is related to the following products: