System power, Powering on the system – Brocade NetIron CER 2000 Series Hardware Guide (Supporting R05.6.00) User Manual
Page 56
46
Brocade NetIron CES 2000 Series and NetIron CER 2000 Series Hardware Installation Guide
53-1003029-02
System power
3
System power
After you complete the physical installation of the system, you can power on the system.
Powering on the system
1. Ensure that all power supplies are fully and properly inserted and no power supply slots are
uncovered.
CAUTION
Never leave tools inside the device.
2. Remove the power cord from the shipping package.
3. Attach the AC power cable to the AC connector on the rear panel.
4. Insert the power cable plug into a 115V/120V outlet.
NOTE
To turn the system off, simply unplug the power cords.
NOTE
The socket should be installed near the equipment and should be easily accessible.
NOTE
If the outlet is not rated 115/120V, stop and get the appropriate cable for the outlet.
DANGER
The intra-building ports of the equipment or subassembly is suitable for connection to
intra-building or unexposed wiring or cabling only. The intra-building ports of the equipment or
subassembly MUST NOT be metallically connected to interfaces that connect to the OSP or its
wiring. These interfaces are designed for use as intra-building interfaces only (Type 2 or Type 4
ports as described in GR-1089-CORE, Issue 4) and require isolation from the exposed OSP
cabling. The addition of Primary Protectors is not sufficient protection in order to connect these
interfaces metallically to OSP wiring.
DANGER
Before crimping the ground wire into the provided ground lug insure the bare copper wire has
been cleaned and antioxidant is applied to the bare wire.
DANGER
To insure adequate bonding when attaching the ground lug, a minimum of 20 PSI of torque is
required to be applied to the mounting hardware used to attach the ground lug.