beautypg.com

Wiring the analog output modules, Wiring the pwm output modules, Caution – Yokogawa PC-Based MX100 User Manual

Page 22

background image

IM MX100-0E

Wiring the Analog Output Modules

External power supply

Voltage

V+

Load

+ 24 V

power supply

(when using current output)

Direction of

current

Vext

Current

I+

Load

CAUTION

Two power supply terminals are connected internally. Therefore, do not connect a
separate external power supply to them as fire can result.

Main Output Specifications

Terminal type:

Clamp, attached and removed in units of 4 channels

Load impedance:

Voltage 5 kΩ or more

Current 600 Ω or less

Applicable wire size: 0.08 to 2.5 mm

2

(AWG28 to 12)

Wiring the PWM Output Modules

External power supply

Pulse width output

V+

Load

+

4-28 V

power supply

CAUTION

Two power supply terminals are connected internally. Therefore, do not connect a
separate external power supply to them as fire can result.

Main Output Specifications

Output capacity:

1A/ch max, however, 4 A or less total for all modules

*1, *2

Terminal type:

Clamp, attached and removed in units of 4 channels

Applicable wire size: 0.08 to 2.5 mm

2

(AWG28 to 12)

*1

A 1A current limit circuit is built in to the output circuit. Once the current limit circuit is ON,
the circuit continues to operate unless the external power supply is turned OFF.

*2 This module has a built-in fuse. The built-in fuse protects against fires or abnormal

emissions of heat due to load shortages or other abnormalities.

Signal Wiring of the MX100