Communication (serial) > basic settings, Status relay – Yokogawa Button Operated MV2000 User Manual

Page 57

background image

Communication (Ethernet) > Modbus client > Auto setting

Setting

Selectable Range or Choices

Default Value

Auto setting of MODBUS client will be

executed.
The following settings will be cleared.

OK?

Yes/No

Communication (Serial) > Basic settings

Setting

Selectable Range or Choices

Default Value

Serial

Baud rate

1200/2400/4800/9600/19200/38400

9600

Data length

7/8

8

Parity

Odd/Even/None

Even

Handshaking

Off:Off/XON:XON/XON:RS/CS:RS

Off:Off

Address

Numeric value (1 to 99)

1

Protocol

Normal/Modbus/Modbus-M

Normal

Communication (Serial) > Modbus master >Basic settings

Setting

Selectable Range or Choices

Default Value

Modbus master basic settings

Read cycle

125ms/250ms/500ms/1s/2s/5s/10s

1s

Timeout

125ms/250ms/500ms/1s/2s/5s/10s/1min

1s

Retrials

Off/1/2/3/4/5/10/20

1

Inter-block delay

Off/5ms/10ms/15ms/45ms/100ms

Off

Auto recovery

Off/1min/2min/5min/10min/20min/30min/1h

2min

Communication (Serial) > Modbus master > Command settings

Setting

Selectable Range or Choices

Default Value

Master command number

1-8/9-16

1-8

1 to 16

Off/R/R-M/W/W-M

Off

Master > First

Varies depending on the send command type

Master > Last

Varies depending on the send command type

Slave > Address

Numeric value (1 to 247)

1

Slave > Registers

Numeric value (register number)

R, R-M:30001
W, W-M: 40001

Slave > Type

INT16/UINT16/INT32_B/INT32_L/UINT32_B/

R, R-M, W: INT16

UINT32_L/FLOAT_B/FLOAT_L

W-M: INT32_B

Status relay

Setting

Selectable Range or Choices

Default Value

Status relay

Memory/Media status

On/Off

Off

Measurement error

On/Off

Off

Communication error

On/Off

Off

Memory stop

On/Off

Off

End

Setting

Selectable Range or Choices

Default Value

Do you want to store and make the new

settings take effect?

Yes/No/Cancel

Default MV2000 Settings

5

IM MV2000-02E