beautypg.com

Meas channel > moving average, Meas channel > color, Meas channel > zone, scale, bar graph – Yokogawa Button Operated MV2000 User Manual

Page 39: Meas channel > partial

background image

Setting

Selectable Range or Choices

Default Value

Range > Alarm 1 to 4

On/Off

Off

Type

H/L/h/l/R/r/T/t

H

Value

Numeric value

0.00

Relay On/Off

On/Off

Off

No.

I01 to I06/I11 to I16/S01 to S30

I01

Detect

On/Off

On

Meas channel > Tag, Memory sample, Alarm delay

Setting

Selectable Range or Choices

Default Value

First-CH, Last-CH

Numeric value (channel number) 1 to 48

001

Tag > Characters

Character string (up to 16 characters)

Memory sample > On/Off

On/Off

On

Alarm delay > Time

Numeric value (1 to 3600) s

10

Meas channel > Moving average

Setting

Selectable Range or Choices

Default Value

First-CH, Last-CH

Numeric value (channel number) 1 to 48

001

Moving average > On/Off

On/Off

Off

Count

Numeric value (2 to 400)

2

Meas channel > Color

Setting

Selectable Range or Choices

Default Value

Group of channel

001–010/011–020/021–030/031–040/041–048

001-010

Color

Red, Green Blue, B.violet, Brown, Orange, Y.green,

Lightblue, Violet, Gray, Lime, Cyan, Darkblue, Yellow,

Lightgray, Purple, Black, Pink, L.brown, L.green,

Darkgray, Olive, DarkCyan, S.green

Colors assigned in order to

groups
Red, Green Blue, B.violet, Brown,

Orange, Y.green, Lightblue,

Violet, Gray

Meas channel > Zone, Scale, Bar graph

Setting

Selectable Range or Choices

Default Value

First-CH, Last-CH

Numeric value (channel number) 1 to 48

001

Zone

Lower

Numeric value (0 to 95) %

0

Upper

Numeric value (5 to 100) %

100

Scale

Position

Off/1/2/3/4/5/6/7/8/9/10

1

Division

4/5/6/7/8/9/10/11/12/C10

10

Bar graph

Base position

Normal/Center/Lower/Upper

Normal

Division

4/5/6/7/8/9/10/11/12

10

Meas channel > Partial

Setting

Selectable Range or Choices

Default Value

First-CH, Last-CH

Numeric value (channel number) 1 to 48

001

Partial

On/Off

On/Off

Off

Expand

Numeric value (1 to 99)%

50

Boundary

Numeric value (minimum span value + 1 digit to

maximum span value – 1 digit)

0.0000

Default MV2000 Settings

39

IM MV2000-02E

This manual is related to the following products: