Wiring clamped terminals – Yokogawa Button Operated MV2000 User Manual
Page 25
Wiring Clamped Terminals
Remove the terminal block.
Hold both ends of the
terminal block and
pull straight.
Input signal wire
First, loosen the screw at the front using a
flat-blade screwdriver. Insert the input signal
wire into the slit on the left side of the terminal
block, and fasten the screw at the front.
Recommended wire size
0.08 to 1.5 mm
2
(AWG28 to 16)
Recommended length
of stripped wire:
7 mm
Connect the wires.
Flat-blade
screwdriver
Hold both ends of the terminal
block, align it with the connector,
and then push it in.
Connect the terminal block.
Note
RTD input terminals A and B are isolated on each channel. Terminal b is shorted internally
across all channels. However, terminal b is also isolated on each channel on models with the
/N1 option (Cu10, Cu25 RTD input/3-wire isolated RTD) and /N2 option (3-wire isolated RTD).
Connecting Input Cables
25
IM MV2000-02E