Math channel > Math start action

Setting

Selectable Range or Choices

Default Value

Math start action > Math start

Off/Start/Rst+St

Start

Ext. channel > Range, Alarm

Setting

Selectable Range or Choices

Default Value

First-CH, Last-CH

Numeric value (external input channel number) 201

to 440

201

Ext. range

On/Off

On/Off

Off

Span Lower

Numeric value (–30000 to 30000, decimal place 0 to 4) –200.00

Span Upper

Numeric value (–30000 to 30000, decimal place 0 to 4) 200.00

Unit

Character string (up to 6 characters)

Ext. alarm

1 to 4

On/Off

Off

Type

H/L/T/t

H

Value

Numeric value

0.00

Relay On/Off

On/Off

Off

Number

I01 to I06/I11 to I16/S01 to S30

I01

Detect

On/Off

On

Ext. channel > Tag, Memory sample, Alarm delay

Setting

Selectable Range or Choices

Default Value

First-CH, Last-CH

Numeric value (external input channel number) 201 to

440

201

Tag > Characters

Character string (up to 16 characters)

Memory sample

On/Off

Off

Alarm delay > Time

Numeric value (1 to 3600) s

10

Ext. channel > Color

Setting

Selectable Range or Choices

Default Value

Group of channel

201–210/211–220/221–230/.../421–430/431–440

201–210

Color

Red, Green Blue, B.violet, Brown, Orange, Y.green,

Lightblue, Violet, Gray, Lime, Cyan, Darkblue, Yellow,

Lightgray, Purple, Black, Pink, L.brown, L.green,

Darkgray, Olive, DarkCyan, S.green

Colors assigned in order to

groups.
Red, Green Blue, B.violet,

Brown, Orange, Y.green,

Lightblue, Violet, Gray

Ext. channel > Zone, Scale, Bar graph

Setting

Selectable Range or Choices

Default Value

First-CH, Last-CH

Numeric value (external input channel number) 201 to

440

201

Zone

Lower

Numeric value (0 to 95) %

0

Upper

Numeric value (5 to 100) %

100

Scale

Position

Off/1/2/3/4/5/6/7/8/9/10

1

Division

4/5/6/7/8/9/10/11/12/C10

10

Bar graph

Base position

Normal/Center/Lower/Upper

Normal

Division

4/5/6/7/8/9/10/11/12

10

Ext. channel > Partial

Setting

Selectable Range or Choices

Default Value

First-CH, Last-CH

Numeric value (external input channel number) 201

to 440

201

Partial

On/Off

On/Off

Off

Expand

Numeric value (1 to 99)%

50

Boundary

Numeric value (minimum span value + 1 digit to

maximum span value – 1 digit)

0.00

Default MV2000 Settings

42

IM MV2000-02E