beautypg.com

Menu tab, Alarm, Burnout, rjc – Yokogawa Button Operated MV2000 User Manual

Page 51

background image

Menu Tab

Alarm

Setting

Selectable Range or Choices

Default Value

Basic setting

Reflash

On/Off

Off

Rate of change > Decrease

1 to 32

1

Rate of change > Increase

1 to 32

1

Indicator

Hold/Nonhold

Nonhold

Switch, Relay

Internal Switch > AND

None/S01/S01-S02/…/S01-S29/S01-S30

None

Relay > AND

None/I01/I01-I02/…/I01-I15/I01-I16

None

Relay > Action

Energize/De_energize

Energize

Relay > Hold

Hold/Nonhold

Nonhold

Relay > Relay Action on ACK

Normal/Reset

Normal

Hysteresis

Meas CH > High/Low

Numeric value (0.0 to 5.0)

0.5

Meas CH > Delta High/Low

Numeric value (0.0 to 5.0)

0.0

Math CH > High/Low

Numeric value (0.0 to 5.0)

0.0

Ext. CH > High/Low

Numeric value (0.0 to 5.0)

0.0

A/D, Memory

Setting

Selectable Range or Choices

Default Value

Scan interval > Scan mode

Normal/Fast

Normal

Normal > Scan interval

125ms/250ms (MV2008)

125ms

1s/2s/5s (MV2010, MV2020, MV2030, MV2040, MV2048)

1s

Normal > A/D integrate

Auto/50Hz/60Hz/100ms

Auto

Fast > Scan interval

25ms (MV2008)

25ms

125ms (MV2010, MV2020, MV2030, MV2040, MV2048)

125ms

Fast > A/D integrate

600Hz

600Hz

Memory

Data kind

Display/E+D/Event

Event

Burnout, RJC

Setting

Selectable Range or Choices

Default Value

First-CH, Last-CH

Numeric value (channel number) 001 to 048

001

Burnout

Mode

Off/Up/Down

Off

RJC

Mode

Internal/External

Internal

Volt

Numeric value (–20000 to 20000)µV

0

Default MV2000 Settings

51

IM MV2000-02E