Setting Mode Settings and Default Values

Menu Tab

Meas channel > Range, Alarm

Setting

Selectable Range or Choices

Default Value

First-CH, Last-CH

Numeric value (channel number) 1 to 48

001

Range>Mode

Skip/Volt/TC/RTD/Scale/Delta/DI/1-5V/Sqrt

Volt

Mode=Volt

Range

20mV/60mV/200mV/2V/6V/20V/50V

2V

Span Lower

Numeric value (depends on the range)

–2.0000

Span Upper

Numeric value (depends on the range)

2.0000

Mode=TC

Range

R/S/B/K/E/J/T/N/W/L/U/WRe

R

Span Lower

Numeric value (depends on the range)

0.0

Span Upper

Numeric value (depends on the range)

1760.0

Mode=RTD

Range

Pt/JPt

Pt

Span Lower

Numeric value (depends on the range)

–200.0

Span Upper

Numeric value (depends on the range)

600.0

Mode=Scale

Type

Volt/TC/RTD/DI

Volt

Range

20mV/60mV/200mV/2V/6V/20V/50V (type = Volt)
R/S/B/K/E/J/T/N/W/L/U/WRe (type = TC)
Pt/JPt (type = RTD)
Level/Cont (type = DI)

2V
R
Pt
Level

Span Lower

Numeric value (depends on the range)

–2.0000

Span Upper

Numeric value (depends on the range)

2.0000

Scale Lower

Numeric value (depends on the range)

0.00

Scale Upper

Numeric value (depends on the range)

200.00

Unit

Character string (up to 6 characters)

Mode=Delta

Type

Volt/TC/RTD/DI

Volt

Range

20mV/60mV/200mV/2V/6V/20V/50V (type = Volt)
R/S/B/K/E/J/T/N/W/L/U/WRe (type = TC)
Pt/JPt (type = RTD)
Level/Cont (type = DI)

2V
R
Pt
Level

Span Lower

Numeric value (depends on the range)

–2.0000

Span Upper

Numeric value (depends on the range)

2.0000

Ref. CH

Numeric value (measurement channel number)

001

Mode=DI

Range

Level/Cont

Level

Span Lower

Numeric value (0, 1)

0

Span Upper

Numeric value (0, 1)

1

Mode=1-5V

Range

1-5V

1-5V

Span Lower

Numeric value (0.800 to 5.200)

1.000

Span Upper

Numeric value (0.800 to 5.200)

5.000

Scale Lower

Numeric value (–30000 to 30000, decimal place 0 to 4) 0.00

Scale Upper

Numeric value (–30000 to 30000, decimal place 0 to 4) 200.00

Unit

Character string (up to 6 characters)

Low-cut

On/Off

Off

Mode=Sqrt

Range

20mV/60mV/200mV/2V/6V/20V/50V

2V

Span Lower

Numeric value (depends on the range)

–2.0000

Span Upper

Numeric value (depends on the range)

2.0000

Scale Lower

Numeric value (–30000 to 30000, decimal place 0 to 4) 0.00

Scale Upper

Numeric value (–30000 to 30000, decimal place 0 to 4) 200.00

Unit

Character string (up to 6 characters)

Low-cut

On/Off

Off

Low-cut value

0.0 to 5.0 (%)

0.5