Setting Mode Settings and Default Values
Menu Tab
Meas channel > Range, Alarm
Setting
Selectable Range or Choices
Default Value
First-CH, Last-CH
Numeric value (channel number) 1 to 48
001
Range>Mode
Skip/Volt/TC/RTD/Scale/Delta/DI/1-5V/Sqrt
Volt
Mode=Volt
Range
20mV/60mV/200mV/2V/6V/20V/50V
2V
Span Lower
Numeric value (depends on the range)
–2.0000
Span Upper
Numeric value (depends on the range)
2.0000
Mode=TC
Range
R/S/B/K/E/J/T/N/W/L/U/WRe
R
Span Lower
Numeric value (depends on the range)
0.0
Span Upper
Numeric value (depends on the range)
1760.0
Mode=RTD
Range
Pt/JPt
Pt
Span Lower
Numeric value (depends on the range)
–200.0
Span Upper
Numeric value (depends on the range)
600.0
Mode=Scale
Type
Volt/TC/RTD/DI
Volt
Range
20mV/60mV/200mV/2V/6V/20V/50V (type = Volt)
R/S/B/K/E/J/T/N/W/L/U/WRe (type = TC)
Pt/JPt (type = RTD)
Level/Cont (type = DI)
2V
R
Pt
Level
Span Lower
Numeric value (depends on the range)
–2.0000
Span Upper
Numeric value (depends on the range)
2.0000
Scale Lower
Numeric value (depends on the range)
0.00
Scale Upper
Numeric value (depends on the range)
200.00
Unit
Character string (up to 6 characters)
—
Mode=Delta
Type
Volt/TC/RTD/DI
Volt
Range
20mV/60mV/200mV/2V/6V/20V/50V (type = Volt)
R/S/B/K/E/J/T/N/W/L/U/WRe (type = TC)
Pt/JPt (type = RTD)
Level/Cont (type = DI)
2V
R
Pt
Level
Span Lower
Numeric value (depends on the range)
–2.0000
Span Upper
Numeric value (depends on the range)
2.0000
Ref. CH
Numeric value (measurement channel number)
001
Mode=DI
Range
Level/Cont
Level
Span Lower
Numeric value (0, 1)
0
Span Upper
Numeric value (0, 1)
1
Mode=1-5V
Range
1-5V
1-5V
Span Lower
Numeric value (0.800 to 5.200)
1.000
Span Upper
Numeric value (0.800 to 5.200)
5.000
Scale Lower
Numeric value (–30000 to 30000, decimal place 0 to 4) 0.00
Scale Upper
Numeric value (–30000 to 30000, decimal place 0 to 4) 200.00
Unit
Character string (up to 6 characters)
—
Low-cut
On/Off
Off
Mode=Sqrt
Range
20mV/60mV/200mV/2V/6V/20V/50V
2V
Span Lower
Numeric value (depends on the range)
–2.0000
Span Upper
Numeric value (depends on the range)
2.0000
Scale Lower
Numeric value (–30000 to 30000, decimal place 0 to 4) 0.00
Scale Upper
Numeric value (–30000 to 30000, decimal place 0 to 4) 200.00
Unit
Character string (up to 6 characters)
—
Low-cut
On/Off
Off
Low-cut value
0.0 to 5.0 (%)
0.5
Default MV2000 Settings