beautypg.com

Recording and saving, Recording and saving -3, Index recording and saving – Yokogawa Removable Chassis DX1000N User Manual

Page 8

background image

1-3

IM 04L41B01-03E

Description of the Multi Batch Function

1

2

3

Index

Recording and Saving

Starting and Stopping Recording (Memory Sampling)

You can start and stop recording for each batch group individually. Or, you can start and
stop recording across all batch groups simultaneously.

Feature

Operation Example

Report

Relay output

Instrument

information

output

Computation Starting

computation

using the

START key

(Math start

of the Math

start action)

Batch Group 1

Batch Group 2

Batch Group 3

Simultaneous start
Simultaneous stop

Start

Start

Stop

Start

Stop

Start

Stop

Stop

Start

Stop

Off

Start

Reset + Start

Relay output when recording

stops

Reset and start computation

Do not start computation

Start computation

Recording

Start and stop batch groups individually

Simultaneous start and stop

• Starting and Stopping a Report (/M1 and /PM1 Option)

The report feature starts when you start recording on any batch group and it stops

when all batch groups stop recording.

• Starting and Stopping Computation (/M1 and /PM1 Option)

• All computations start and stop together at the same time.
• When computations are stopped, you can start recording and computation at the

same time.

Math Start Action

Action

Start

Starts computation.

Reset+Start

When starting

each batch group

separately

Resets the values calculated on the

selected batch group’s computation

channels

*

.

Only the flags being used on the

computation channels are cleared to zero.
The DX then starts computation again.

When starting

all batch groups

simultaneously

Resets the values calculated on all

computation channels for the batch groups

that are not recording

*

.

Only the flags being used on the

computation channels are cleared to zero.
The DX then starts computation again.

* The computation channels registered to that batch group’s display group.

• You can stop computation at any time.

1.1 Recording and Saving Data

This manual is related to the following products: