beautypg.com

Loading display and event data, Using the func key – Yokogawa Removable Chassis DX1000N User Manual

Page 31

background image

3-10

IM 04L41B01-03E

• Loading Display and Event Data

Even when in batch overview mode, you can use the following procedure to load

display or event data and display the corresponding historical trend.
MENU (to switch to setting mode), and select the File tab > Load display data or

Load event data > press the CF or USB soft key > select the file and press DISP/
ENTER

Take note of the following points regarding loading of data.

• You can load any batch group’s data.
• The historical trend is displayed on batch group 1’s historical trend screen. When

the display is split into two windows, batch group 1’s trend is displayed as the
current trend.

• If you select Exit from the display selection menu and finish displaying the historical

trend, the DX returns to batch overview mode.

• Using the FUNC Key

You can use the FUNC key for the following operations. For operating procedures,

see the reference for each respective operation. Entries marked with a * function the
same as in batch single mode.

Operation Name

Description

Reference

*

Alarm ACK

Executes alarm acknowledgement for all

activated alarms.

Section 3.8 in the User’s Manual.

*

Alarm display reset

Resets the alarm display.

Section 3.12 in the User’s Manual.

*

Media eject

Puts the external memory into a state in

which it can be safely removed from the DX.

Operation Guide.

*

Snapshot

Saves the screen image data from the

active display to a CF card (in PNG format).

Section 6.6 in the User’s Manual.

*

Manual sample

Saves the instantaneous values of all

channels.

Section 6.5 in the User’s Manual.

*

Save stop

Aborts the manual data saving operation in

progress.

Section 4.8 in the User’s Manual.

Math start/stop

Starts or stops computations on all

computation channels.

Section 3.2 in this manual.

Computation reset

Resets computed results for all computation

channels.

Section 3.2 in this manual.

*

Math ACK

Clears the computation data dropout display. Section 9.4 in the User’s Manual.

*

Edge switch

Sets the event edge switch to on.

Section 7.1 in the User’s Manual.

*

Timer reset

Resets the relative timer.

Section 7.1 in the User’s Manual.

*

Match timer reset

Resets the single match time timer.

Section 7.1 in the User’s Manual.

*

Key lock

Locks or unlocks keys.

Section 8.1 in the User’s Manual.

*

Logout

Logs off from the DX.

Section 8.3 in the User’s Manual.

*

Locked ACK

Executes the Locked ACK operation.

Advanced Security Manual.

*

Password change

Changes the password used to log on to the

DX.

Section 8.3 in the User’s Manual.

Text field

Displays the text field for the batch group

that you select.

Section 3.8 in this manual.

*

Builder screen

Displays the custom display’s builder

screen.

IM04L41B01-04E.

*

Favorite registration Registers the current display as a favorite.

Section 3.7 in this manual.

*

Standard display

Registers the current display as the

standard DX display.

Section 5.14 (DX1000)
Section 5.15 (DX2000)
in the User’s Manual

System info

Displays the system information screen.

Section 2.5 in the User’s Manual.

Network info

Displays the network information screen.

Section 2.5 in the User’s Manual.

*

SNTP

Synchronizes the DX’s time with an SNTP

server.

Section 1.8 in the Communication

Manual.

*

E-Mail start/stop

Starts or stops e-mail transmission.

Section 1.4 in the Communication

Manual.

*

E-Mail test

Confirms sending of e-mail and the details

of the transmission.

Section 1.4 in the Communication

Manual.

*

FTP test

Checks the connection between the DX and

the FTP server.

Section 1.7 in the Communication

Manual.

3.4 Using Batch Overview Mode

This manual is related to the following products: