Yokogawa Removable Chassis DX1000N User Manual
Page 27
3-6
IM 04L41B01-03E
3.2 Starting, Stopping, and Resetting
Computations (/M1 and /PM1 Options)
• All computations start and stop together at the same time. You cannot start or stop
computations for each batch group separately.
• You can reset the values calculated on computation channels separately for each
batch group.
• When you reset a calculated value, the flags in use are also reset to zero.
Procedure
• Starting Recording and Computation Simultaneously
You can start recording and computation simultaneously by using the START key
(Math start action) when Math start is set to Start or Reset+Start. For the operating
procedure, see section 9.4 in the User’s Manual.
When recording is started (see section 3.1), computation also starts at the same time.
• Starting Only the Computation
Follow the procedure below when the batch overview mode screen is displayed.
1.
In operation mode, press
FUNC.
The FUNC key menu appears.
2.
Press the
Math start soft key.
Computation starts, and the computation icon is displayed in the status display section.
• Stopping the Computation
Follow the procedure below when the batch overview mode screen is displayed.
1.
In operation mode, press
FUNC.
The FUNC key menu appears.
2.
Press the
Math stop soft key.
Computation stops, and the computation icon in the status display section disappears.
Note
• Stopping recording does not simultaneously stop computations.
• When you stop computations, the calculated value for computation channels is retained
as the value held immediately prior to computation stopping. When recording, this retained
value is recorded.
• Resetting Calculated Values
Starting Recording and Resetting and Starting a Computation All at the
Same Time
For information on starting recording and resetting and starting a computation all at
the same time, see section 1.1.
Resetting the Values Calculated on All Computation Channels
Follow the procedure below when the batch overview mode screen is displayed.
1.
Press
FUNC.
The FUNC key menu appears.
2.
Press the
Math reset soft key.
The values calculated on all computation channels are reset, and all flags are cleared to
zero.