2.1 Settings for the Multi Batch Function

Specialized Settings for the Multi Batch Function

Enabling the Multi Batch Function

First, enable the Multi Batch function. The measured data in internal memory is cleared
when you enable or disable the Multi Batch function. However, updating the number of
batches used with the Multi Batch function does not clear the measured data in internal
memory.

Settings for Each Batch Group

The settings you can change for each batch group are as follows. You can find these
settings on the Multi batch tab in setting mode.
Display group, Trip line, File header, Data file name, and Batch text

General Settings Other Than the Specialized Settings for the Multi Batch

Function

The settings in setting mode excluding those on the Multi batch tab, and the settings in
basic setting mode are common to all batch groups.

Scan Mode

You cannot set the scan mode to FAST.

Event Actions

When the Multi Batch function is enabled, a portion of the actions in the event action
function requires the designation of a specific batch group. For those types of actions, a
box containing all the batch groups for you to select from is displayed.

Actions that require

the designation of a

specific batch group

MemoryStart/Stop, MemoryStart, MemoryStop, Message, SaveDIsplay,

SaveEvent, MathReset, DisplayGroupChange.

Timer and Match Time Timer

For DXs with the Multi Batch function, you can use 12 timers and 12 match time timers.

Fixed Features

You cannot change the following settings.

Feature

Setting

Trend rate switching

Fixed to Off.

Trend clear

Fixed to On.

Precautions:

If even one batch group is recording, the following settings cannot be changed.
• Measurement range and memory sampling on/off for measurement channels.
• Expressions, constants, memory sampling on/off, and TLOG for computation channels

(/M1 and /PM1 options).

• Measurement range and memory sampling on/off for external input channels (on

DX2000s with the /MC1 option).

• Trend interval.
• Event data.

The following settings cannot be changed while their applicable batch group is recording.
• Batch text
• Display group
• Trip line
For information about changing settings during recording on DXs with the /AS1 advanced
security option, see section 6.4 in the User’s Manual.