beautypg.com

Yokogawa DO402 Dissolved Oxygen Analyzer User Manual

Page 60

background image

IM 12J05D02-01E

5-24 Parameter setting

Control and Alarm Functions

Control output (mA)

:

Pl control on the 2nd mA output.

The 2nd mA output can be configured to give a P/I (proportional and integral)

control output.

The setpoint, proportional band and integral time are each fully

programmable.

- Adjustable parameters

: Setpoint, proportional range and integral time.

Process alarm

: The contact will be switched when the process value reaches a limit.

This can either be a high or low limit.

- Adjustable parameters

: Setpoint for the process value Hysteresis of the switching action Delay time of

the relay (0 to 200 s)

PI duty cycle control (Fig. 1)

: The contact is used to control the time a solenoid valve is opened.

The propor tional control is achieved by opening and closing the solenoid valve

and varying the ratio of on and off time (on, off).

- Adjustable parameters

: Setpoint, proportional range and integral time. Total period of the pulse period

(5 to 100 s)

PI pulse frequency control (Fig. 2)

: The contact is used to control a pulse-driven pump.

The frequency of pulses regulates the pump speed.

- Adjustable parameters

: Setpoint, proportional range & integral time. Maximum pulse frequency (50 to

120/min.)

Wash cleaning of sensors (Fig. 3)

: Contact S3 is used to control the wash cycle, or as a process alarm.

- Adjustable parameters

: Cleaning time or washing time (tw) Recovery time after washing (tr) Interval

time for wash cycle.

The graph shows a typical response curve during washing. The wash and

recovery times need to be set to suit the process.

Fault alarm

: Contact S4 by default set to function as an alarm, indicating that the EXA has

found a fault in the measuring loop. If the self diagnostics of the EXA indicate

a fault or error, the FAIL contact will be switched. In most cases this will be

caused by a malfunction of the measuring loop.

The FAIL contact is also closed when the power is removed.

The “FAIL” contact may also be configured as a fourth process alarm.