9. General Specifications

9.1 Standard Specifications

Refer to IM 01C25T02-01E for FOUNDATION

Fieldbus communication type and IM 01C25T04-

01EN for PROFIBUS PA communication type for

the items marked with “◊”.

Performance Specifications

See General Specifications sheet, GS 01C25K01-

01EN or GS 01C31K01-01EN.

Functional Specifications

Span & Range Limits

Capsule

Differential

Pressure Span

Water

Equivalent

Flow l/min

Air

Equivalent

Flow Nl/min

F

1 to 5 kPa

{100 to 500 mmH

2

O}

0.016 to 5.0 0.44 to 140

M

2 to 100 kPa

{200 to 10000 mmH

2

O} 0.022 to 23.0 0.63 to 635

H

20 to 210 kPa

{2000 to 21000 mmH

2

O} 0.07 to 33.0

2.0 to 910

Output “◊”

Two wire 4 to 20 mA DC output with digital

communications, linear or square root

programmable. BRAIN or HART FSK protocol

are superimposed on the 4 to 20 mA signal.

Output range: 3.6 mA to 21.6 mA

Output limits conform to NAMUR NE43 can be

pre-set by option C2 or C3.

Failure Alarm “◊”

Output status at CPU failure and hardware

error;

Up-scale: 110%, 21.6 mA DC or more

(standard)

Down-scale: –5%, 3.2 mA DC or less

Note: Applicable for Output signal code D and E

Damping Time Constant (1st order)

Amplifier damping time constant is adjustable

from 0 to 100.00 seconds and added to

response time.

Note: For BRAIN protocol type, when amplifier damping

is set to less than 0.5 seconds, communication

may occasionally be unavailable during the

operation, especially while output changes

dynamically. The default setting of damping

ensures stable communication.

Update Period “◊”

Differential Pressure: 45 ms

Static Pressure: 360 ms

Zero Adjustment Limits

Zero can be fully elevated or suppressed, within

the lower and upper range limits of the capsule.

External Zero Adjustment “◊”

External Zero is continuously adjustable with

0.01% incremental resolution of span. Re-range

can be done locally using the digital indicator

with range-setting switch.

Integral Indicator (LCD display)

5-digit Numerical Display, 6-digit Unit Display

and Bar graph.

The indicator is configurable to display one or

up to four of the following variables periodically.;

Differential pressure in %, Scaled Differential

pressure, Differential Pressure in Engineering

unit, Static Pressure in Engineering unit.

See “Setting When Shipped” for factory setting.

Burst Pressure Limits (Differential pressure

transmitter part)

69 MPa (10000 psi)

Normal Operating Condition

(Selected features may affect limits.)

Ambient Temperature Limits

–40 to 85°C (–40 to 185°F)

–30 to 80°C (–22 to 176°F) with LCD display

Process Temperature Limits

–40 to 120°C (–40 to 248°F)

Ambient Humidity Limits

0 to 100% RH