beautypg.com

Installation, 1 precautions, 2 mounting – Yokogawa EJX115A User Manual

Page 23: Installation -1, Precautions -1, Mounting -1, Important

background image

<4. Installation>

4-1

IM 01C25K01-01E

4. Installation

4.1 Precautions

Before installing the transmitter, read the cautionary

notes in section 2.4, “Selecting the Installation

Location.” For additional information on the

ambient conditions allowed at the installation

location, refer to subsection 9.1 “Standard

Specifications.”

IMPORTANT

• When welding piping during construction,

take care not to allow welding currents to

flow through the transmitter.

• Do not step on this instrument after

installation.

4.2 Mounting

The transmitter can be mounted on a nominal

50 mm (2-inch) pipe using the mounting

bracket supplied, as shown in figure 4.1 and

4.2 The transmitter can be mounted on either a

horizontal or a vertical pipe.

When mounting the bracket on the transmitter,

tighten the (four) bolts that hold the transmitter

with a torque of approximately 39 N·m {4kgf·m}.

The transmitter is shipped with the manifold set

up as per the order specifications.

For correct flow measurement, the flow path

must always be filled with fluid; otherwise,

measurement accuracy cannot be assured.

For the vertical impulse piping type, it is

recommended that the manifold be mounted

facing up for liquid flow measurement; facing

down for gas flow measurement, as shown in

Figure 4.2.

Figure 4.1 and 4.2 shows the mounting of the

transmitter for horizontal piping and vertical piping

with using the mounting bracket.

Horizontal pipe mounting

Vertical pipe mounting

Transmitter

mounting bolt

U-bolt nut

Mounting bracket

U-bolt nut

Mounting bracket

50 mm(2-inch) pipe

50 mm(2-inch) pipe

U-bolt

U-bolt

F0401.ai

Transmitter

mounting bolt

Figure 4.1

Transmitter Mounting

(Horizontal Impulse Piping Type)