A2-5 – Yokogawa EJA440E User Manual
Page 95
A2-5
IM 01C25T01-06EN
Checklist (5/5)
No.
Items
Parameters
Result
Example
10-b
Simulation of Blockage detection operation
• Close completely the valve for the side where
the alarm of Invalid Reference Value is not
generated.
For the case that the high-pressure side value is
closed;
• Record the values of
fDP, fSPl, fSPh, BlkF,
and
DPAvg after the certain time,
(
Diag Period X Diag Supp Count), passed.
*: Record the value after checked that the
status is “GOOD”.
fDP*
7.48562E-09
fSPh*
7.14085E-09
For the case that the low-pressure side value is
closed;
• Record the values of
fDP, fSPl, fSPh, BlkF,
and
DPAvg after the certain time,
(
Diag Period X Diag Supp Count), passed.
*: Record the value after checked that the
status is “GOOD”.
fDP*
7.48562E-09
fSPI*
7.23277E-09
• Record the status of Checkbox in
Diag
Option.
• Check that the alarms status of “B Blocking” is
set.
Note:
If the alarm of “ILBD over range” is generated,
the valve may be closed too much tightly. Open
valve a little and record the updated status of the
parameters.
Diag Option
A Blocking
Large Fluct L
Large Fluct H
L Side Blocking
H Side Blocking
B Blocking
Invalid Ref F
Invalid Ref SPH
Invalid Ref SPL
Invalid Ref DP
ILBD over range
• Check that the alarm of “B Blocking” is not
generated.
Diag Error
B Blocking