Yokogawa EJA440E User Manual
Page 82
<5. Parameter Summary>
5-4
IM 01C25T01-06EN
Function
Label
Item
Contents
Default value Handling
*
1
Display setup Bar Indicator
Bar indicator
Off or On
On
W
Chg power on info
Change the LCD display when
powering on
On or Off
M
Disp Out 1
LCD output 1
PRES, PRES %,
ENGR.PRES, SP, SP %
PRES %
W
Disp Out 2
LCD output 2
PRES, PRES %,
ENGR.PRES, SP, SP % or
Not used
Not used
W
Disp Out 3
LCD output 3
(Ditto)
Not used
W
Disp Out 4
LCD output 4
(Ditto)
Not used
W
Disp Pres % fnctn
% display mode
Linear or Sq root
As specified or
Linear
W
Disp
Pres
% Reso
% display resolution
Normal or High resolution
Normal
W
Engr exp
User set exponent
---, x10, x100, x1000
--- or as
specified
W
Engr LRV
User set lower range value
Unit specified in Set Engr Unit As specified
W
Engr point
Decimal place for user set
0 to 4
2
W
Engr URV
User set upper range value
Unit specified in Set Engr Unit As specified
W
Modify Engr Unit
User set engineering unit
M
Pres disp point
Decimal place for differential
pressure
0 to 4
2
W
Set Engr Unit
Engineering unit select
M
SP disp point
Decimal place for static pressure
0 to 4
2
WD
Squawk
HART 7
Squawk
Specify the device under the
communication (turn the LCD
on).
M
Error log
Error log Clear
Clear error records
M
Error log view
Error records
Log1 (latest) to log4
M
Event
Notification
Event Notification
Control
HART 7
Event Notification
(Enable event notification on
token-passing data link layer,
Off)
Off
W
Device Status
Mask
HART 7
Event Masking
W
Status group 1 to
10 Mask
HART 7
Ext dev status
Mask
HART 7
Device Diagnostic
Status 0 Mask
HART 7
Device Diagnostic
Status 1 Mask
HART 7
AO saturated Mask
HART 7
AO fixed Mask
HART 7
Set Event
Notification Timing
HART 7
Configure Event Notification Timing Configure Event Notification
Retry Time, Event Max
Update Time and Event
Debounce Interval
M
*1:
Handling:
R=Read only, W=Read & Write, M=Method, A=Applicable for option code AL, G=Applicable for option code DG6,
D=Applicable for differential pressure transmitters. Do not change these parameters for pressure transmitters.
*2:
Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)
*3:
The default value shows MWP (Maximum working pressure) of the capsule.
Since the working pressure limit varies according to the Model, refer to the General Specifications section in each user’s manual.