<5. Parameter Summary>

5-4

IM 01C25T01-06EN

Function

Label

Item

Contents

Default value Handling

*

1

Display setup Bar Indicator

Bar indicator

Off or On

On

W

Chg power on info

Change the LCD display when

powering on

On or Off

M

Disp Out 1

LCD output 1

PRES, PRES %,

ENGR.PRES, SP, SP %

PRES %

W

Disp Out 2

LCD output 2

PRES, PRES %,

ENGR.PRES, SP, SP % or

Not used

Not used

W

Disp Out 3

LCD output 3

(Ditto)

Not used

W

Disp Out 4

LCD output 4

(Ditto)

Not used

W

Disp Pres % fnctn

% display mode

Linear or Sq root

As specified or

Linear

W

Disp

Pres

% Reso

% display resolution

Normal or High resolution

Normal

W

Engr exp

User set exponent

---, x10, x100, x1000

--- or as

specified

W

Engr LRV

User set lower range value

Unit specified in Set Engr Unit As specified

W

Engr point

Decimal place for user set

0 to 4

2

W

Engr URV

User set upper range value

Unit specified in Set Engr Unit As specified

W

Modify Engr Unit

User set engineering unit

M

Pres disp point

Decimal place for differential

pressure

0 to 4

2

W

Set Engr Unit

Engineering unit select

M

SP disp point

Decimal place for static pressure

0 to 4

2

WD

Squawk

HART 7

Squawk

Specify the device under the

communication (turn the LCD

on).

M

Error log

Error log Clear

Clear error records

M

Error log view

Error records

Log1 (latest) to log4

M

Event

Notification

Event Notification

Control

HART 7

Event Notification

(Enable event notification on

token-passing data link layer,

Off)

Off

W

Device Status

Mask

HART 7

Event Masking

W

Status group 1 to

10 Mask

HART 7

Ext dev status

Mask

HART 7

Device Diagnostic

Status 0 Mask

HART 7

Device Diagnostic

Status 1 Mask

HART 7

AO saturated Mask

HART 7

AO fixed Mask

HART 7

Set Event

Notification Timing

HART 7

Configure Event Notification Timing Configure Event Notification

Retry Time, Event Max

Update Time and Event

Debounce Interval

M

*1:

Handling:

R=Read only, W=Read & Write, M=Method, A=Applicable for option code AL, G=Applicable for option code DG6,

D=Applicable for differential pressure transmitters. Do not change these parameters for pressure transmitters.

*2:

Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)

*3:

The default value shows MWP (Maximum working pressure) of the capsule.

Since the working pressure limit varies according to the Model, refer to the General Specifications section in each user’s manual.

This manual is related to the following products: