<3. Parameter Setting>

3-32

IM 01C25T01-06EN

b) Acknowledge Event Notification
Execute

Acknowledge Event Notification

method.

1) Set to Enter Event Number is in confirmed

Event Number a)5.

2) OK.

3) Set “Trans 1: Send Acknowledge” to Select

Transaction.

4) OK.

5) Confirm Event Status is 0x00.

(3) Event Notification Record

• Procedure to call up the display

DD and DTM

[Root Menu] → Detailed setup →

Output condition →HART output

→ Burst condition → Event

Notification → Knowledge →

→ Acknowledge

Event Notification

Acquisition of the event number

and approval.

a) Get Event Number
Confirm the latest event number.

Execute

Acknowledge Event Notification

method.

1) Enter Event Number is set to “0”.

2) OK.

3) Set “Trans 0: Read Event Notificaiton” to

Select Transaction.

4) OK.

5) Confirm Event Number.

b) Confirmation record of Event Notification
Confirm four events checked in a).

Execute

Acknowledge Event Notification

method.

1) Enter the event number to Enter Event

Number which is confirmed in a)5.

2) OK.

3) Set “Trans 0: Read Event Notificaiton” to

Select Transaction.

4) OK.

5) Knowledge menu displays events record.

Ex.) When the confirmed event number is 123.

Event Number

Explanation

123

The latest event

122

An event before the once.

121

An event before the twice.

120

An event before three times.

3.3.17 Multidrop Mode

3.3.17.1 Setting on HART 5

HART 5

“Multidropping” transmitters refer to the connection

of several transmitters to a single communication

transmission line. Up to 15 transmitters can be

connected when set in the multidrop mode. To

activate multidrop communication, the transmitter

address must be changed to a number from 1 to

15. This change deactivates the 4 to 20 mA analog

output, sending it to 4 mA. The alarm current is also

disabled.

Setting of Multidrop Mode

(1) Polling address

• Procedure to call up the display

DD and DTM

(excluding EJX_

HART 5[1.2])

[Root Menu] → Detailed setup →

Output condition → HART output

EJX_HART 5[1.2]

DTM

Configuration → HART →

→ Poll addr

Enter the number from 1 to 15

(2) Enabling the Multidrop Mode of

Configuration Tool

About the procedure to call up the

Polling

display, please refer to the User’s Manual of each

configuration tool.

NOTE

When the same polling address is set for

two or more transmitters in multidrop mode,

communication with these transmitters is

disabled.

(3) Communication when set in multidrop

mode.

• The HART configuration tool searches for a

transmitter that is set in multidrop mode when

it is turned on. When the HART configuration

tool is connected to the transmitter, the polling

address and the tag will be displayed.

• Select the desired transmitter. After that, normal

communication to the selected transmitter is

possible. However, the communication speed

will be slow.

To release multidrop mode, call up the

Poll addr

display and set the address to “0”.