<4. Diagnostics>
4-17
IM 01C25T01-06EN
4.2.2.10 Tuning
When the pressure fluctuation amplitude in fluids is
not sufficiently large or an alarm is often generated
according to the process condition, tune up by
changing the threshold for the blockage detection
(Limit parameters) or the sampling period (
Diag
Period) to enhance the accuracy of the blockage
detection The ILBD operation must be stopped to
tune up. Set “Stop” to
Diag Mode.
Threshold Value
The figure below shows the image of tuning effect
with a monochrome bar.
(a) The tuning image of the threshold values for
(1)
Ratio fDP: Sqrt (fDP/Ref fDP),
(2)
Ratio fSPl: Sqrt (fSPl/Ref fSPl),
(3)
Ratio fSPh: Sqrt (fSPh/Ref fSPh)
F0411-1.ai
0
1
3
Threshold (lower side)
Threshold (upper side)
(1)
Lim fDPmin
(2)
Lim fSPlmin
(3)
Lim fSPhmin
(1)
Lim fDPmax
(2)
Lim fSPlmax
(3)
Lim fSPhmax
(b) The tuning image of the threshold values for
(4) Sqrt (
BlkF/Ref BlkF)
F0411-2.ai
0
-1
1
Threshold (lower side)
Threshold (upper side)
(4)
Lim BlkFmin
(4)
Lim BlkFmax
Figure 4.8
Tuning Image of Threshold Value
Move the threshold toward the white.
• It becomes increasingly likely to give a false
alarm due to the disturbance from environment
change.
• If flow/differential pressure is below
Lim
DPAvgmin or exceeds Lim DPAvgmax,
pressure fluctuation is likely too small or too
large to detect the blockage.
Move the threshold toward the black.
• It enables to be insusceptible to disturbance
such as environment change and to detect the
blockage easier.
• It becomes giving an alarm of the blockage after
the blockage has been progressed.
(1) Setting by DD and DTM (excluding EJX
HART 5 DTM based on FDT1.2)
• Procedure to call up the
threshold related
display
DD and DTM
(excluding
EJX_HART
5[1.2])
[Root Menu] → Diag/Service → Diag
Parameters → ILBD parameters →
Configuration → Diag Lim →
The default values at the factory setting are the
values of
Lim fDPmax to Lim BlkFmin shown in
Table 4.3.
Change the threshold value to solve your problem
according to the above image.
1) Set “Stop” to
Set Diag Mode.
2) Change the unsuitable value of
Diag Lim
parameters corresponding to the each
blockage detection.
Note: Set to “Calculation” after setting the parameter.
Limit parameter
#
Parameter
Threshold value
[1] Lim fDPmax
Threshold to detect “A
Blocking” by using
Ratio fDP
[2] Lim fDPmin
Threshold to detect “B
Blocking” by using
Ratio fDP
[3] Lim fSPlmax
Threshold to detect “Large
Fluct L” by using
Ratio fSPl
[4] Lim fSPlmin
Threshold to detect “L Side
Blocking” by using
Ratio fSPl
[5] Lim fSPhmax
Threshold to detect “Large
Fluct H” by using
Ratio fSPh
[6] Lim fSPhmin
Threshold to detect “H Side
Blocking” by using
Ratio fSPh
[7] Lim BlkFmax
Threshold to detect “H Side
Blocking” by using
BlkF
[8] Lim BlkFmin
Threshold to detect “L Side
Blocking” by using
BlkF
(2) Setting by EJX HART 5 DTM based on
FDT1.2
Combination of threshold depend on the sensitivity
of blockage detection can be selected from High,
Medium, or Low in the
Sensitivity parameter.
• Procedure to call up the display
EJX HART 5
DTM based on
FDT1.2
Diag and Service → Advanced
Diag Configuration → Impulse Line
Blockage Detection → Threshold →
sensitivity
When select “Custom” in the Sensitivity parameter,
you can set each threshold individually.
Set the
Diag Mode to “Stop” before changing the
threshold.