beautypg.com

12 ilbd parameter list, 12 ilbd parameter list -19 – Yokogawa EJA440E User Manual

Page 66

background image

<4. Diagnostics>

4-19

IM 01C25T01-06EN

4.2.2.12 ILBD Parameter List

# Parameter name Default value

Explanation

1 Diag Error

0x0000

The results detected by ILBD or Heat trace monitoring are stored into this

parameter.

Also the condition abnormality in the diagnostic process is stored as an error.

2 Diag Option

0x08FC

The masking in this parameter enable to display each error message and the

status to the output signal or LCD.

The error assigned to each bit is corresponding to that of

Diag Error.

Writable only when Diag Mode is "Stop".

3 Diag Out Option Off

Output mode of 4-20mA when an advanced diagnostic alarm is generated.

There are following three output modes; Off, Burnout, or Fall back.

4 Diag Fixed Out

Val

21.6 mA

Parameter for "Fall back" function in the Diag Out option. The output value of

4-20 mA analog signal is specified when an alarm is generated. The value can be

entered within 3.6 to 21.6 mA.

5 DO Select

Off

The variables for status output are specified to this parameter. When the

advanced diagnostic function (option code /DG6) is installed, the parameters

monitoring in diagnostic process can be also assigned to the status output.

6 Diag Mode

Stop

The operation mode of ILBD is set.

Stop:

The blockage detection is stopped.

Calculate: The blockage detection is carried out.

The alarms are generated along with the detected result.

Reference: The reference values are obtained and the update values are

overwritten.

After setting, this mode moves automatically to "Calculation".

7 Diag Period

180 (s)

The data acquisition period for ILBD is set within 20 to 65535 (s). If the process

fluctuation values are unsteady, this value is changed to the longer to enhance

the accuracy of the blockage detection.

Writable only when Diag Mode is "Stop".

8 Diag Supp Count 3

Detection count to generate an alarm. When the statistical value as

Ratio fDP

and

BlkF exceeds consecutively the threshold by number of times preset to this

parameter, it is estimated that the impulse line is plugged.

9 Diag Description

Memo field. 32 alphanumerics

10 fDP

Average value of the sum of squares of differential pressure fluctuation.

11 fDP Status

Status of

fDP

12 fSPl

Average value of the sum of squares of low-pressure-side static pressure

fluctuation. For gauge/absolute pressure transmitter, 0 is set.

13 fSPl Status

Status of

fSPl

14 fSPh

Average value of the sum of squares of high-pressure-side static pressure

fluctuation. For gauge/absolute pressure transmitter, 0 is set.

15 fSPh Status

Status of

fSPh

16 BlkF

Blockage degree characterized in comparison of high- and low-pressure side

pressure fluctuation value.

17 BlkF Status

Status of

BlkF

18 DPAvg

Ratio of the average of differential pressure/pressure to the maximum span of an

EJX transmitter.

19 DPAvg Status

Status of

DPAvg

20 Ratio fDP

CRatio fDP or NRatio fDP is used by Diag Comp setting.

fDP decreases and this parameter is used to determine whether one or both

sides are plugged.

21 Ratio fDP Status

Status of

Ratio fDP

22 Ratio fSPl

SQRT (

fSPl/Ref fSPl).

fSPl decreases and this parameter is used to determine whether low-pressure-

side is plugged.

23 Ratio fSPl Status

Status of

Ratio fSPl

24 Ratio fSPh

SQRT (

fSPh/Ref fSPh).

fSPh decreases and this parameter is used to determine whether high-pressure-

side is plugged.

25 Ratio fSPh

Status

Status of

Ratio fSPh

26 Ref fDP

Value of

fDP obtained under normal condition.

27 Ref fDP Status

Status of

fDP obtained under normal condition.

This manual is related to the following products: