1 blockage detection, 1 blockage detection -6 – Yokogawa EJA440E User Manual
Page 53
<4. Diagnostics>
4-6
IM 01C25T01-06EN
4.2.2.1 Blockage Detection
Limit parameter
When the parameter based on pressure fluctuation
exceeds the preset value, EJX diagnoses an
impulse line as blockage and gives an alarm. The
threshold values are set to Limit parameter shown
in below table.
• Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
[Root Menu] → Diag/Service
→ Diag Parameters → ILBD
Parameters → Configuration →
Diag Lim →
EJX_HART 5[1.2]
DTM
Diag and Service → Advanced Diag
Configurations → Impulse Line
Blockage Detection → Threshold
→ Sensitivity →
Table 4.2
Limit Parameter
#
Parameter
Threshold value
[1] Lim fDPmax
Threshold to detect “A
Blocking” by using
Ratio fDP
[2] Lim fDPmin
Threshold to detect “B
Blocking” by using
Ratio fDP
[3] Lim fSPlmax
Threshold to detect “Large
Fluct L” by using
Ratio fSPl
[4] Lim fSPlmin
Threshold to detect “L Side
Blocking” by using
Ratio fSPl
[5] Lim fSPhmax
Threshold to detect “Large
Fluct H” by using
Ratio fSPh
[6] Lim fSPhmin
Threshold to detect “H Side
Blocking” by using
Ratio fSPh
[7] Lim BlkFmax
Threshold to detect “H Side
Blocking” by using
BlkF
[8] Lim BlkFmin
Threshold to detect “L Side
Blocking” by using
BlkF
[9] Lim DPAvgmax Threshold to detect “ILDB over
range” by using
DPAvg and to
detect “Invalid Ref xx” by using
Ref DPAvg
[10] Lim DPAvgmin
Threshold to detect “ILDB over
range” by using
DPAvg and to
detect “Invalid Ref xx” by using
Ref DPAvg
Table 4.3 shows the default values at the factory
setting.
NOTE
• When ILBD is performed for the first time,
use the default value. If the pressure
fluctuation amplitude is low or a false alarm
is often generated after ILBD is performed,
change the values of Limit parameters
according to the procedure described in
subsection 4.2.2.10. Tuning