<4. Diagnostics>

4-27

IM 01C25T01-06EN

Table 4.6

HART Configuration Tool Error Messages

Error message

Probable cause

Countermeasure

Invalid selection

Change the setting.

Value was too high

Set value is too high.

Value was too low

Set value is too low.

Too few data bytes received

In write protect mode

Operation is set in the Write Protect mode. —

Lower range value too high

LRV set point is too high.

Change the range.

Lower range value too low

LRV set point is too low.

Upper range value too high

URV set point is too high.

Upper range value too low

URV set point is too low.

Span too small

Set span is too small.

Applied process too high

Applied pressure is too high.

Adjust the applied pressure.

Applied process too low

Applied pressure is too low.

New lower range value pushed upper

range value over upper sensor limit

The shift of URV according to the new LRV

setting exceeds USL.

Change the URV setting within the

range of USL.

Excess correction attemted

Amount of correction is too much.

Adjust the amount.

Lower conversion not succeeded

Characters are not convertible. e.g. %

Correct the setting.

Not in fixed current mode

The fixed current mode is desired but not

set in that mode.

Set in the fixed current mode.

In multidrop mode

Operation is set in the multi-drop mode.

Not write protect mode

Operation is set without a password.

Lower range value and upper range

value out of limits

URV and LRV are out of range limits.

Change the setting.

Table 4.7

Device Status

Item

Description

Field Device Malfunction

(0x80)

Field device has

malfunctioned due to a

hardware error or failure.

Configuration Changed

(0x40)*

A modification has been

made to the configuration

of the field device.

Cold Start

(0x20)

A reset of the field device

has occurred, or power

has been removed and

reapplied.

More Status Available

(0x10)

Field device has more

status available.

Loop Current Fixed

(0x08)

Analog output and its

digital representation

are in fixed mode, and

not responsive to input

changes.

Loop Current Saturated

(0x04)

Analog output and its

digital representation are

outside the operating

range limits, and not

responding to input.

Non-Primary Variable Out

of Limits

(0x02)

Process applied to the

non-primary variable is

outside the operating

limits of the field device.

Primary Variable Out of

Limits

(0x01)

Process applied to the

primary variable is outside

the operating limits of the

field device.

*:

This flag can be reset. Refer to subsection 4.1.3 (6) Reset

Configuration Changed Flag

Table 4.8

Extended Device Status

Item

Description

Maintenance Required

(0x01)

Device requires

maintenance.

Device Variable Alert

(0x02)

Configuration is invalid or

device is under simulation

mode.

Table 4.9

Data Quality and Limit Status

Data Quality

Description

Good

The value may be used in

control.

Poor Accuracy

The quality of the value is

less than normal, but the

value may still be useful.

Manual / Fixed

The value is manually

fixed.

Bad

The value is not useful.

Limit Status

Description

Constant

The value cannot be

changed, no matter what

the process does.

Low Limited

The value is out of the

high or low limit.

High Limited
Not Limited

The value is free to

change.