beautypg.com

7 obtain reference values, 7 obtain reference values -15, Important – Yokogawa EJA440E User Manual

Page 62

background image

<4. Diagnostics>

4-15

IM 01C25T01-06EN

Table 4.4

Requirements to apply ILBD

Condition

fDP

7×10

-10

or more

fSPI

1×10

-10

or more

fSPh

1×10

-10

or more

BlkF

-0.5 to 0.5

fDP is not enough.

No blockage can be detected if

fDP is not larger

than the specified value.

Only fDP is enough.

“A Blocking” or “B Blocking” can be detected

if

fSPl and fSPh are not larger than specified

values.

fDP and fSPl are enough.

“H Side Blocking” and “Large Fluct H” can not

be detected if

fSPh is not larger than specified

value.

fDP and fSPh are enough.

“L Side Blocking” and “Large Fluct L” can not

be detected if

fSPl is not larger than specified

value.

fDP, fSPl and fSPh are enough.

All alarm modes can be detected even if

BlkF is

not within the specified values.

4.2.2.7 Obtain Reference Values

The pressure fluctuation values are reduced

when the impulse line is plugged. Therefore, the

reference value is required to determine the degree

of reduction.

IMPORTANT

• If the impulse line is about to be plugged at

the time when a reference value is obtained,

blockages cannot be detected accurately.

The impulse lines on both the high-pressure

and low-pressure sides need to be cleaned

before a reference value is obtained.

• All air bubbles need to be adequately purged

before a reference value is obtained.

• Reference values must be obtained under

operating condition.

Start of Sampling

The sampling of reference value is carried out for

180 seconds, which is the default value set to

Diag

Period.
1) Confirm that the sampling period (

Diag Period)

is set to 180 seconds.

2) Set “Reference” to

Diag Mode.

The sampling starts soon after the setting.

IMPORTANT

• For the each parameter, the one value is

given. If Reference is set to

Diag Mode

again, the value is updated and overwritten.

• If the power supply is shut down during the

sampling,

Diag Mode becomes “Stop”. Set

“Reference” to

Diag Mode in order to carry

out the sampling again.

End of Sampling

After about 180 seconds, the sampling

automatically finishes. The “Reference” setting of

Diag Mode moves automatically to “Calculation”.
Confirm that the setting of

Diag Mode moves to

“Calculation”.

Reference Values

Confirm the latest values are obtained into the

following parameters.

• Ref fDP

• Ref fSPl

• Ref fSPh

• Ref BlkF

• Ref DPAvg

• Procedure to call up the display

DD and DTM

(excluding EJX_

HART 5[1.2])

[Root Menu] → Diag/Service

→ Diag Parameters → ILBD

parameters → Status → Diag

Reference → Ref fDP/Ref fSPl/Ref

fSPh/Ref BlkF/Ref DPAvg

EJX_HART 5[1.2]

DTM

Diag and Service → Advanced

Diag Configuration → Impulse Line

Blockage Detection → Ref fDP/Ref

fSPl/Ref fSPh/Ref BlkF/Ref DPAvg

This manual is related to the following products: