<2. Connection>

2-2

IM 01C25T01-06EN

(a) Confirmation on the name plate

The last numerical number engraved after

Serial number and year of production shows

HART protocol revision number at the shipment

which is shown in Figure 2.1.

F0201.ai

: Refer to USER'S MANUAL.

Made in Japan

TOKYO 180-8750 JAPAN

MODEL

SUFFIX

SUPPLY

OUTPUT

MWP

mA DC

V DC

STYLE

CAL

RNG

NO.

XXX - - - XX 

Revision No.

Output Signal

Code

Revision No.

HART Protocol

Revision

J

5

HART 5

7

HART 7

-

HART 7

E

-

HART 5

Figure 2.1 Hart Protocol Revision Number on

Name Plate

(b) Confirmation on integral indicator

(A case of integral indicator code D is specified)

Refer to section 2.1.

(c) Confirmation by using HART configuration tool

1) Connect the configuration tool to the

transmitter.

2) Confirm numerical number displayed on

“Universal rev” column.

• Procedure to call up the display

DD and DTM

(excluding EJX_

HART 5[1.2])

[

Root Menu (refer to 3.1.1) ]

→ Review → Universal rev

EJX_HART 5[1.2]

DTM

Configuration → HART

→Universal rev

IMPORTANT

Protocol revision supported by HART

configuration tool must be the same or higher

than that of the transmitter.

Protcol revision

supported by HART

configuration tool

5

7

Protocol revision of

the transmitter

5

7

×

: Communication OK

× : Communication NG

NOTE

HART 7 communication is supported by

FieldMate R2.02 or later.

NOTE

When the output signal code of the transmitter

is “-J”, HART protocol revision can be changed.

Refer to subsection 3.3.18 about the procedure

of the revision change of HART 5 and HART 7.

2.3 Device Description (DD) on

a Configuration Tool and

Transmitter Device Revision

Before using a HART configuration tool, confirm

that the DD for the transmitter is installed in the

configuration tool.
About the DD, use the device type, device revision

and DD Revision shown in the Table 2.1.

Table 2.1

HART Protocol Revision, Device

Revision and DD Revision

HART

Protocol

Revision

(*1)

DPharp Pressure Transmitter

Model

Device

Type

Device

Revision

DD

Revision

5

EJX series

EJX

(0x51)

3

3

or later

EJA series EJA-NEXT

(0x5C)

1

2

or later

7

EJX series

EJX

(0x3751)

10

2

or later

EJA series EJA-NEXT

(0x375C)

10

1

or later

*1:

When the output signal code is “–E”, only “5” is available.

The device revision of the transmitter and DD can

be confirmed as shown below.
If the correct DD is not installed in the configuration

tool, download it from the official web site of HART

Communication Foundation.
(1) Confirmation of device revision for the

transmitter

● Confirmation on integral indicator

(A case of integral indicator code D is

specified)

Refer to the section 2.1