Transmitter device revision -2, Important – Yokogawa EJA440E User Manual
Page 11
<2. Connection>
2-2
IM 01C25T01-06EN
(a) Confirmation on the name plate
The last numerical number engraved after
Serial number and year of production shows
HART protocol revision number at the shipment
which is shown in Figure 2.1.
F0201.ai
: Refer to USER'S MANUAL.
Made in Japan
TOKYO 180-8750 JAPAN
MODEL
SUFFIX
SUPPLY
OUTPUT
MWP
mA DC
V DC
STYLE
CAL
RNG
NO.
XXX - - - XX
Revision No.
Output Signal
Code
Revision No.
HART Protocol
Revision
J
5
HART 5
7
HART 7
-
HART 7
E
-
HART 5
Figure 2.1 Hart Protocol Revision Number on
Name Plate
(b) Confirmation on integral indicator
(A case of integral indicator code D is specified)
Refer to section 2.1.
(c) Confirmation by using HART configuration tool
1) Connect the configuration tool to the
transmitter.
2) Confirm numerical number displayed on
“Universal rev” column.
• Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
[
Root Menu (refer to 3.1.1) ]
→ Review → Universal rev
EJX_HART 5[1.2]
DTM
Configuration → HART
→Universal rev
IMPORTANT
Protocol revision supported by HART
configuration tool must be the same or higher
than that of the transmitter.
Protcol revision
supported by HART
configuration tool
5
7
Protocol revision of
the transmitter
5
7
×
: Communication OK
× : Communication NG
NOTE
HART 7 communication is supported by
FieldMate R2.02 or later.
NOTE
When the output signal code of the transmitter
is “-J”, HART protocol revision can be changed.
Refer to subsection 3.3.18 about the procedure
of the revision change of HART 5 and HART 7.
2.3 Device Description (DD) on
a Configuration Tool and
Transmitter Device Revision
Before using a HART configuration tool, confirm
that the DD for the transmitter is installed in the
configuration tool.
About the DD, use the device type, device revision
and DD Revision shown in the Table 2.1.
Table 2.1
HART Protocol Revision, Device
Revision and DD Revision
HART
Protocol
Revision
(*1)
DPharp Pressure Transmitter
Model
Device
Type
Device
Revision
DD
Revision
5
EJX series
EJX
(0x51)
3
3
or later
EJA series EJA-NEXT
(0x5C)
1
2
or later
7
EJX series
EJX
(0x3751)
10
2
or later
EJA series EJA-NEXT
(0x375C)
10
1
or later
*1:
When the output signal code is “–E”, only “5” is available.
The device revision of the transmitter and DD can
be confirmed as shown below.
If the correct DD is not installed in the configuration
tool, download it from the official web site of HART
Communication Foundation.
(1) Confirmation of device revision for the
transmitter
● Confirmation on integral indicator
(A case of integral indicator code D is
specified)
Refer to the section 2.1