A2-3 – Yokogawa EJA440E User Manual
Page 93
A2-3
IM 01C25T01-06EN
Checklist (3/5)
Go to the following step according to the result of "Invalid Ref xx" shown in the
Diag Error of 8th check item.
Diag Error
Check
item
Invalid Ref SPH
Invalid Ref SPL
Invalid Ref DP
→
10-a
→
10-b
: The alarm is generated.
: The alarm is not generated.
No.
Items
Parameters
Result
Example
10-a
Simulation of Blockage detection operation
• H Side Blocking: 10-a-1
• L Side Blocking: 10-a-2
• Both Side Blocking: 10-a-3
10-a-1 H Side Blocking
• Close the high-pressure side valve
completely.
• Record the values of
fDP, fSPl, fSPh, BlkF,
and
DPAvg after the certain time,
(
Diag Period X Diag Supp Count), passed.
*: Record the value after checked that the
status is “GOOD”.
fDP*
7.48562E-09
fSPI*
7.23277E-09
fSPh*
7.14085E-09
BlkF
-0.287259
• Record the status of Checkbox in
Diag
Option.
• Check that the alarms status of “A Blocking”
and “H Side Blocking” are set.
Note: If the alarm of “ILBD over range” is generated,
the valve may be closed too much tightly. Open
valve a little and record the updated status of the
parameters.
Diag Option
A Blocking
Large Fluct L
Large Fluct H
L Side Blocking
H Side Blocking
B Blocking
Invalid Ref F
Invalid Ref SPH
Invalid Ref SPL
Invalid Ref DP
ILBD over range
• Check that the alarm of “H Side Blocking” is
generated.
• Check that the alarm of “L Side Blocking” is
not generated.
Diag Error
L Side Blocking
H Side Blocking