Checklist (3/5)

Go to the following step according to the result of "Invalid Ref xx" shown in the

Diag Error of 8th check item.

Diag Error

Check

item

Invalid Ref SPH

Invalid Ref SPL

Invalid Ref DP

10-a

10-b

: The alarm is generated.

: The alarm is not generated.

No.

Items

Parameters

Result

Example

10-a

Simulation of Blockage detection operation

• H Side Blocking: 10-a-1

• L Side Blocking: 10-a-2

• Both Side Blocking: 10-a-3

10-a-1 H Side Blocking

• Close the high-pressure side valve

completely.

• Record the values of

fDP, fSPl, fSPh, BlkF,

and

DPAvg after the certain time,

(

Diag Period X Diag Supp Count), passed.

*: Record the value after checked that the

status is “GOOD”.

fDP*

7.48562E-09

fSPI*

7.23277E-09

fSPh*

7.14085E-09

BlkF

-0.287259

• Record the status of Checkbox in

Diag

Option.

• Check that the alarms status of “A Blocking”

and “H Side Blocking” are set.

Note: If the alarm of “ILBD over range” is generated,

the valve may be closed too much tightly. Open

valve a little and record the updated status of the

parameters.

Diag Option
A Blocking

Large Fluct L

Large Fluct H

L Side Blocking

H Side Blocking

B Blocking

Invalid Ref F

Invalid Ref SPH

Invalid Ref SPL

Invalid Ref DP

ILBD over range

• Check that the alarm of “H Side Blocking” is

generated.

• Check that the alarm of “L Side Blocking” is

not generated.

Diag Error
L Side Blocking

H Side Blocking