SpecView from Watlow

 31 

Watlow Addendum

Adjust the Displayed Decimals

The following procedures describe how to adjust the number of decimal places displayed in SpecView.

Note this procedure does not apply to EZ-ZONE controllers communicating with SpecView by Watlow
EZ-ZONE Standard Bus because with that protocol the decimal places are automatically displayed
according to the controller setting.

To make the number of decimal places displayed in SpecView match the controller display:

1) Set the decimal

setting in the
controller as desired.
(See the table for
details about each
controller.

For This Controller…

For Sensor Type…

Parameter in
SpecView…

Parameter in
Controller…

Available
Decimals

EZ-ZONE ST, PM, RM

Any

N/A

dEC

0 to 3

MICRODIN

Any

Decimal Point

(No Display)

0 or 1

SERIES 96

Thermocouple, RTD

Decimal Pt 1

dEC1

0 or 1

Process

Decimal Pt 1

dEC1

0 to 3

SERIES 97

Any

Decimal 1

dEC1

0 or 1

SERIES SD Controller
SERIES SD Limit

Thermocouple, RTD

See Note

1

dEC

0 or 1

Process (mA, mV, V)

See Note

2

dEC

0 to 3

POWER SERIES

Not available

986, 987, 988, 989

Any

Decimal 1
Decimal 2

dEC1

0 to 3

SERIES F4 Ramping

Thermocouple, RTD,
Wet Bulb-Dry Bulb

Input 1 DecPlaces
Input 2 DecPlaces
Input 3 DecPlaces

Choose
Decimal

0 or 1

Process

Input 1 DecPlaces
Input 2 DecPlaces
Input 3 DecPlaces

Choose
Decimal

0 to 3

CLS, MLS,
CLS200, MLS300

Thermocouple, RTD

Precision

Disp Format

1

Linear

Precision

Disp Format

0 to 4

1

For a SERIES SD with a thermocouple or RTD set the Decimals (Ctlr Temp Display Only) parameter, the
Decimals (SpecView and Ctlr Prcs Display) parameter and SpecView for the same number of decimals.

2

For a SERIES SD with a process input (mA, mV or V) set the Decimals (SpecView and Ctlr Prcs Display)
parameter and SpecView for the same number of decimals.