Adjust the displayed decimals – Watlow SpecView from Watlow User Manual
Page 31
SpecView from Watlow
31
Watlow Addendum
Adjust the Displayed Decimals
The following procedures describe how to adjust the number of decimal places displayed in SpecView.
Note this procedure does not apply to EZ-ZONE controllers communicating with SpecView by Watlow
EZ-ZONE Standard Bus because with that protocol the decimal places are automatically displayed
according to the controller setting.
To make the number of decimal places displayed in SpecView match the controller display:
1) Set the decimal
setting in the
controller as desired.
(See the table for
details about each
controller.
For This Controller…
For Sensor Type…
Parameter in
SpecView…
Parameter in
Controller…
Available
Decimals
EZ-ZONE ST, PM, RM
Any
N/A
dEC
0 to 3
MICRODIN
Any
Decimal Point
(No Display)
0 or 1
SERIES 96
Thermocouple, RTD
Decimal Pt 1
dEC1
0 or 1
Process
Decimal Pt 1
dEC1
0 to 3
SERIES 97
Any
Decimal 1
dEC1
0 or 1
SERIES SD Controller
SERIES SD Limit
Thermocouple, RTD
See Note
1
dEC
0 or 1
Process (mA, mV, V)
See Note
2
dEC
0 to 3
POWER SERIES
Not available
986, 987, 988, 989
Any
Decimal 1
Decimal 2
dEC1
0 to 3
SERIES F4 Ramping
Thermocouple, RTD,
Wet Bulb-Dry Bulb
Input 1 DecPlaces
Input 2 DecPlaces
Input 3 DecPlaces
Choose
Decimal
0 or 1
Process
Input 1 DecPlaces
Input 2 DecPlaces
Input 3 DecPlaces
Choose
Decimal
0 to 3
CLS, MLS,
CLS200, MLS300
Thermocouple, RTD
Precision
Disp Format
1
Linear
Precision
Disp Format
0 to 4
1
For a SERIES SD with a thermocouple or RTD set the Decimals (Ctlr Temp Display Only) parameter, the
Decimals (SpecView and Ctlr Prcs Display) parameter and SpecView for the same number of decimals.
2
For a SERIES SD with a process input (mA, mV or V) set the Decimals (SpecView and Ctlr Prcs Display)
parameter and SpecView for the same number of decimals.