 12 

Watlow Addendum

Decimal Places

Specify zero (0) to display whole numbers for parameters such as process variable and set point. Specify
one (1) to display these parameters with tenths precision, two (2) to display hundredths and so on. With
Modbus TCP networks you must include the decimal setting in the address string. For a Modbus RTU
network if the decimal place setting and comma delimiter are omitted, SpecView will display whole
numbers. Valid settings range from zero (0) to four (4).

Register Address Offset

The register address offset is the sum of the First Instance Address for the specific EZ-ZONE product,
any applicable Instance Offsets and the Gateway Offset, if any. The tables below give the First Instance
Address and Instance Offset for each instrument and product. The Gateway Offset is set by the user
when the RUI Gateway or RM Access Module gateway is configured. The First Instance Address and
Instance Offsets depend on the controller’s data map setting.

Gateway Offset

Be careful not to set up instruments that attempt to read Modbus registers that are mapped over by the
configuration of the gateway.

Register Addresses and Offsets for EZ-ZONE ST

Instrument

Instances

Data Map 1 via RUI Only*

Data Map 2**

First

Instance

Address

Instance

Offset

First

Instance

Address

Instance

Offset

EZ-ZONE Alarm

1 to 2

1480

50

1450

60

EZ-ZONE Analog Input

1 to 2

360

160

360

90

EZ-ZONE Control Loop

1

N/A

N/A

1750

N/A

EZ-ZONE Communications

1

2418

N/A

2060

20

EZ-ZONE Current

1

1120

N/A

1240

N/A

EZ-ZONE Digital I/O

1 to 6

880

30

940

30

EZ-ZONE Limit

1

680

N/A

720

N/A

EZ-ZONE Profile (Map 1)**

1 to 4

6070

500

N/A

N/A

EZ-ZONE Profile (Map 2)**

1 to 4

N/A

N/A

4000

1000

EZ-ZONE Profile (ST Map 1)

1 to 4

2870

800

N/A

N/A

EZ-ZONE Profile Operation

1

2720

N/A

3800

N/A

EZ-ZONE Set Points

1

2160

N/A

1890

N/A

*Supported only via EZ-ZONE RUI Gateway. **Available with firmware version 4.0 or later.

Register Addresses and Offsets for EZ-ZONE PM

Instrument

Instances

Data Map 1

Data Map 2

First

Instance

Address

Instance

Offset

First

Instance

Address

Instance

Offset

EZ-ZONE Alarm

1 to 4

1480

50

1880

60

EZ-ZONE Analog Input

1 to 2

360

80

360

90

EZ-ZONE Communications

1 or 2

2490

20

2970

20

EZ-ZONE Control Loop

1 to 2

1880

70

2360

70

EZ-ZONE Current

1

1120

N/A

1360

N/A

EZ-ZONE Digital I/O

1 to 12

880

30

1000

30

EZ-ZONE Limit

1

680

N/A

720

N/A

EZ-ZONE Profile (Map 1)

1 to 4

2570

500

N/A

N/A

EZ-ZONE Profile (Map 2)

1 to 4

N/A

N/A

4500

1000

EZ-ZONE Profile Operation

1

2520

N/A

4340

N/A

EZ-ZONE Set Points

1 to 2

2160

80

2640

80