Decimal places, Register address offset, Gateway offset – Watlow SpecView from Watlow User Manual
Page 12: Register addresses and offsets for, Ez-zone st, Ez-zone pm
SpecView from Watlow
12
Watlow Addendum
Decimal Places
Specify zero (0) to display whole numbers for parameters such as process variable and set point. Specify
one (1) to display these parameters with tenths precision, two (2) to display hundredths and so on. With
Modbus TCP networks you must include the decimal setting in the address string. For a Modbus RTU
network if the decimal place setting and comma delimiter are omitted, SpecView will display whole
numbers. Valid settings range from zero (0) to four (4).
Register Address Offset
The register address offset is the sum of the First Instance Address for the specific EZ-ZONE product,
any applicable Instance Offsets and the Gateway Offset, if any. The tables below give the First Instance
Address and Instance Offset for each instrument and product. The Gateway Offset is set by the user
when the RUI Gateway or RM Access Module gateway is configured. The First Instance Address and
Instance Offsets depend on the controller’s data map setting.
Gateway Offset
Be careful not to set up instruments that attempt to read Modbus registers that are mapped over by the
configuration of the gateway.
Register Addresses and Offsets for EZ-ZONE ST
Instrument
Instances
Data Map 1 via RUI Only*
Data Map 2**
First
Instance
Address
Instance
Offset
First
Instance
Address
Instance
Offset
EZ-ZONE Alarm
1 to 2
1480
50
1450
60
EZ-ZONE Analog Input
1 to 2
360
160
360
90
EZ-ZONE Control Loop
1
N/A
N/A
1750
N/A
EZ-ZONE Communications
1
2418
N/A
2060
20
EZ-ZONE Current
1
1120
N/A
1240
N/A
EZ-ZONE Digital I/O
1 to 6
880
30
940
30
EZ-ZONE Limit
1
680
N/A
720
N/A
EZ-ZONE Profile (Map 1)**
1 to 4
6070
500
N/A
N/A
EZ-ZONE Profile (Map 2)**
1 to 4
N/A
N/A
4000
1000
EZ-ZONE Profile (ST Map 1)
1 to 4
2870
800
N/A
N/A
EZ-ZONE Profile Operation
1
2720
N/A
3800
N/A
EZ-ZONE Set Points
1
2160
N/A
1890
N/A
*Supported only via EZ-ZONE RUI Gateway. **Available with firmware version 4.0 or later.
Register Addresses and Offsets for EZ-ZONE PM
Instrument
Instances
Data Map 1
Data Map 2
First
Instance
Address
Instance
Offset
First
Instance
Address
Instance
Offset
EZ-ZONE Alarm
1 to 4
1480
50
1880
60
EZ-ZONE Analog Input
1 to 2
360
80
360
90
EZ-ZONE Communications
1 or 2
2490
20
2970
20
EZ-ZONE Control Loop
1 to 2
1880
70
2360
70
EZ-ZONE Current
1
1120
N/A
1360
N/A
EZ-ZONE Digital I/O
1 to 12
880
30
1000
30
EZ-ZONE Limit
1
680
N/A
720
N/A
EZ-ZONE Profile (Map 1)
1 to 4
2570
500
N/A
N/A
EZ-ZONE Profile (Map 2)
1 to 4
N/A
N/A
4500
1000
EZ-ZONE Profile Operation
1
2520
N/A
4340
N/A
EZ-ZONE Set Points
1 to 2
2160
80
2640
80