List of device addresses – Proface APL3000B - Node Box PC User Manual

Page 74

background image

Chapter 3 PS-A Monitoring Features

3-23

„ List of Device Addresses

*1

When monitoring the voltage with the device monitor, the unit is “mV”.

*2

When monitoring the number of revolutions with the device monitor, the unit is “rpm”.

*3

When monitoring Temperature with the device monitor, the unit is “°C”.

*4

Used for only the system to read/write the data and perform monitoring operation.

*5

Shuts down and restarts the operation system on the client PS-A.

*6

Indicates the error event that is being monitored by the PS-A.

Device

Device

Type

Device

Symbol

Read/

Write

Bit Access

16-bit

Access

32-bit

Access

VcoreA*

1

WORD

VLT

Read

VLT0

+3.3V*

1

WORD

VLT2

+5.0V*

1

WORD

VLT3

+12V*

1

WORD

VLT4

-12V*

1

WORD

VLT6

Number of Revolution of
System FAN *

2

WORD

FAN

FAN1

System Temperature *

3

WORD

TMP

TMP0

CPU Temperature *

3

WORD

TMP1

DIN

WORD

DIN

DIN00-DIN01

DIN0

DOUT

WORD

DOUT

Read/

Write

DOUT00-DOUT01

DOUT0

Error Event

WORD

ERR

Read

ERR00-ERR10

ERR0
ERR1

Internal Memory Area *

4

WORD

LS

Read/

Write

LS00000-LS0000F

to

LS02550-LS0255F

LS0000

to

LS0255

LS0000

to

LS0254

Shared Memory

WORD

PL

PL00000-PL0000F

to

PL02550-PL0255F

PL0000

to

PL0255

PL0000

to

PL0254

Software Reset Port *

5

WORD

RST

RST0

Error Mask *

6

WORD

ERRM

Read

ERRM00-ERRM10

ERRM0
ERRM1

• When “Forced Shutdown” or “Forced Reboot” is written to the device address, the

system automatically shuts down/restarts the operation system without prompting

the confirmation for saving the data on current applications.

Take extra cautions when performing write operation in order to avoid accidental

data loss.

Value to be Written

Operation

Decimal Number

Hexadecimal Number

1

0001

Shutdown

2

0002

Reboot

257

0101

Forced Shutdown

258

0102

Forced Reboot