o 15. Monitor the voltage at terminals 3 and 2 or
the current at terminal 4 of terminal block TB1,
as well as the brake current on terminal 1 of
terminal block TB2.
a. If using a sensor: As the roll diameter
decreases, the sensor voltage or current will
decrease which will cause the brake torque to
decrease, keeping the tension proportional to the
roll size.
b. If using a PLC: As the roll diameter
decreases, the analog signal from the PLC must
decrease to keep the tension proportional to the
roll size.
o 16. After an initial run has been completed,
remove power from the system and wait
approximately 30 seconds before proceeding to
the next step.
o 17. Remove the meter from between the sense
magnet lead to terminal 1 of terminal block TB2
and tighten the terminal screw.
o 18. Disconnect the second voltmeter from
terminals 2 and 3 of terminal block TB1.
o 19. Reapply power to the control system.
o 20. If the remote mode selector switch is used,
repeat steps 5 through 17, using the remote
mode selector switch.
Note: If start-up and adjustment procedures do
not provide the desired results, consult the
troubleshooting section of this manual.
o 21. Close the cover of the TCS-200-1 and latch
by tightening the screw that is provided.