REV 3 EZCT S2 USER’S MANUAL
51
5.2
Verifying the EZCT S2’s V
x
Sense Circuit Using an External Meter
The excitation voltage (V
x
) sensed by the EZCT S2 can be verified using an external RMS volt
meter. Follow the steps below to verify the EZCT S2’s V
x
sense circuit:
a. Connect the X cables to an RMS volt meter as shown in Figure 13.
b. Select the EZCT S2’s Diagnostics mode (see section 5.1).
c. Press the
[PAPER ∧ Contrast]
key to raise the V
x
voltage.
d. Verify the V
x
voltage displayed on the EZCT S2 LCD screen against the value displayed on
the external volt meter.
e. Press the
[STOP]
key to end the test.
Figure 13. EZCT S2 V
x
Verification Test Connections
See also other documents in the category Vanguard Accessories for electrical:
- Resistor Transducer Adapter 9095-UC (7 pages)
- Accu-Ohm 200 S2 (4 pages)
- Accu-Trans (28 pages)
- ATO-400 (43 pages)
- ATO-400P (44 pages)
- Auto-Ohm (22 pages)
- Auto-Ohm 100_200 s2 (31 pages)
- Auto‐Ohm 200 S3 (66 pages)
- DMOM-100 (35 pages)
- DMOM-100_200 s2 (42 pages)
- DMOM-200 (33 pages)
- Herculito (17 pages)
- ATRT-01 S2 (59 pages)
- ATRT-01_01B S3 (88 pages)
- ATRT-01_01B_01D (31 pages)
- ATRT-03_03A (114 pages)
- ATRT-03_03A S2 (147 pages)
- CVT-765 (46 pages)
- Tri-Phase (155 pages)
- CBCT (14 pages)
- CBPS-300 (16 pages)
- CT-3500 (24 pages)
- CT-3500 S2 (53 pages)
- CT-6500 (69 pages)
- CT-6500 S2 (82 pages)
- CT-7000 (83 pages)
- CT-7000 S2 (108 pages)
- CT-7000 S3 (137 pages)
- CT-7500 (76 pages)
- CT-7500 S2 (110 pages)
- CT-8000 (120 pages)
- CT-8000 S3 (145 pages)
- DigiTMR (86 pages)
- DigiTMR S2 (123 pages)
- DigiTMR S2 PC (31 pages)
- MCCB-250 (17 pages)
- UPS S2 (13 pages)
- EZCT-2000 (68 pages)
- EZCT-2000 (45 pages)
- EZCT-2000A (103 pages)
- EZCT-2000B (118 pages)
- EZCT-2000C Plus (119 pages)
- EZCT-S2A (98 pages)
- IRM-5000P (58 pages)