CT-7000 Operating Instructions

47

9.11 Set-Up Open Analysis Points

Table 16.0 Setting Up "OPEN" Analysis Points Using Distance

STEP

OPERATION

ACTION

DISPLAY

1

SELECT SET UP MENU.

PRESS # 3 KEY.

1. ANALYSIS POINT

2. MEASUREMENT UNITS

3. SAVE / RESTORE

4. NEXT PAGE

2

SELECT ANALYSIS POINT.

PRESS # 1 KEY.

1. OPEN TIMING

2. CLOSE TIMING

3. PRINT SETTING

4. TEST PLAN

3

SELECT OPEN TIMING.

PRESS # 1 KEY.

OPEN ANALYSIS PT 1

1. PERCENT OF STROKE

2. DISTANCE FROM CLOSE

3. CONTACT #1

4

SELECT DISTANCE FROM CLOSE.

PRESS # 2 KEY.

OPEN ANALYSIS PT 1

DISTANCE FROM CLOSE

VALUE: XX.XX in

"ENTER" TO CONFIRM

5

ENTER 1 INCH.

PRESS KEYS 0-9 TO

SET 1.00. USE THE

“ENTER” KEY TO

CONFIRM.

OPEN ANALYSIS PT 1

DISTANCE FROM CLOSE

VALUE: 01.00 in

"ENTER" TO CONFIRM

6

CONFIRM ENTRY.

PRESS THE "ENTER"

KEY.

OPEN ANALYSIS PT 2

1. PERCENTAGE OF STROKE

2. DISTANCE FROM CLOSE

3.CONTACT +/- TIME

7

SELECT DISTANCE FROM CLOSE.

PRESS # 2 KEY.

OPEN ANALYSIS PT 2

DISTANCE FROM CLOSE

VALUE: XX.XX in

"ENTER" TO CONFIRM

8

ENTER 2 INCHES.

PRESS KEYS 0-9 TO

SET 2.00 INCHES.

OPEN ANALYSIS PT 2

DISTANCE FROM CLOSE

VALUE: 02.00 in

"ENTER" TO CONFIRM

9

RETURN TO MAIN MENU.

PRESS THE "ENTER"

KEY.

1.TIME BRKR

2.GET RSLT

3.SET UP

4.DIAGNOSTICS